14 parameterising the v/f characteristic control, Parameterising the v/f characteristic control, 5motor control & motor settings – Lenze i700 User Manual
Page 136: Stop
5
Motor control & motor settings
5.14
Parameterising the V/f characteristic control
136
Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.14
Parameterising the V/f characteristic control
In case of the V/f characteristic control (VFCplus), the motor voltage of the inverter is determined by
means of a linear or quadratic characteristic depending on the field frequency or motor speed to be
generated. The voltage follows a preselected characteristic.
Initial commissioning steps
After the motor and controller have been optimally adjusted to each other, the following "initial
commissioning steps" are sufficient for a simple V/f characteristic control.
1.
Defining the V/f characteristic shape
2.
Activating the voltage vector control (lmin controller)
– or alternatively –
3.
4.
Defining the behaviour at the current limit (Imax controller)
Optimising the control mode
The following "optimisation steps" can be used to further optimise the control mode of the V/f
characteristic control and adapt it to the practical application:
1.
2.
Setting the oscillation damping
3.
Manual test mode "Current pulse"
• Only required if the voltage vector control is applied, or if DC-injection braking or the flying
restart process is activated.
Stop!
• The V/f characteristic control is only suitable for asynchronous motors.
• Observe the following when you actuate drives with a square-law V/f characteristic:
• Please always check whether the corresponding drive is suitable for operation with
a quadratic V/f characteristic!
• If your pump drive or fan drive is not suitable for operation with a square-law V/f
characteristic, use the linear V/f characteristic instead, or select the servo control.
• For adjustment, observe the thermal performance of the connected asynchronous
motor at low output frequencies.
• Usually, standard asynchronous motors with insulation class B can be operated for
a short time with their rated current in the frequency range 0 Hz ... 25 Hz.
• Contact the motor manufacturer to get the exact setting values for the max.
permissible motor current of self-ventilated motors in the lower speed range.
• For square-law V/f characteristics we recommend setting a smaller V
min
.
• As regards the motor nameplate data, at least the rated speed (
for axis B) and the rated frequency (
or
for axis B) must be entered
for the i700 servo inverter to calculate the correct number of pole pairs.