0x60e0 | 0x68e0 - positive torque limit value, 0x60e1 | 0x68e1 - negative torque limit value, 3 signal flow – Lenze i700 User Manual

Page 206: Signal flow, 0x60e0, 0x68e0, 0x60e1, 0x68e1, 7cia402 device profile, Ctrl

Advertising
background image

7

CiA402 device profile

7.8

Cyclic sync position mode (csp)

206

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Tip!
For an interpolation cycle of 2 ms, for instance, the following values are to be set:

• Subindex 1 (Time period value) = "2"
• Subindex 2 (Time index) = "-3"

0x60E0 | 0x68E0 - Positive torque limit value

0x60E1 | 0x68E1 - Negative torque limit value

7.8.3

Signal flow

[7-5]

Signal flow of the servo control in cyclic sync position mode (simplified representation)

100 % ≡ rated motor torque (

0x6076

or

0x6876

for axis B)

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

3276.7 100.0 %

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

UNSIGNED_16

100 % ≡ rated motor torque (

0x6076

or

0x6876

for axis B)

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

3276.7 100.0 %

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

UNSIGNED_16

Interpolation

I

q

I

d

M

CTRL

Target position

Velocity offset

Torque offset

Position

controller

Speed controller: Load value

Position actual value

Controlword

Lenze control word

Modes of operation

Statusword

Lenze status word

Modes of operation display

Positive torque limit value

Negative torque limit value

Speed

limitation

Speed

controller

Torque
limitation

Encoder

evaluation

Field-orientated
control

Torque actual value

Velocity actual value