CiA402 device profile

7.11

Touch probe (TP)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.11.3

Filtering the touch probe signal

A common filter time (debounce time) can be parameterised for the touch probe inputs in order to

debounce the TP signals so that there is no response to external interference signals.

• Every 31 μs, the signal status at the TP input is detected for the debounce filter and a new value

is assigned to the filter.

• Via the following object, the filter time for all touch probe inputs of both axes of the device is

set. A separate setting for a touch probe or an axis is not possible.

0x2500 - Touch probe (TP): Debounce time

7.11.4

Compensation of runtime delays

In reality, both the input connection in the i700 servo inverter and the touch probe sensor have

runtime delays (latencies) themselves. They can be taken into consideration for calculating the

actual tripping time and thus the actual position at the time of tripping.
In the following illustration, the event is detected at the time  in the i700 servo inverter. Due to

the input connection and the sensor used, however, the signal has undergone a runtime delay; the

actual physical event has already occurred at the time . In order to compensate this runtime delay,

a corresponding delay time which is taken into consideration for the determination of the control

cycle and interpolation of the position (see figure

[7-9]

) can be set for each touch probe channel.

[7-10] Compensation of runtime delays (principle)

Note: Since the filter is scanned with 32 kHz, there are discrete, adjustable values. After entering an optional filter

time between 0 and 1984 μs, the value is automatically internally rounded down to the next adjustable value and

is also displayed on read request.

• The filter time is automatically taken into consideration in the TP calculation.

• If the setting is "0", the filter is deactivated.

Setting range

(min. value | unit | max. value)

Lenze setting

0

us

1984 0 us

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16

 Actual physical event
 Electrical recognition of the event in the i700 servo inverter

Delay time between the actual physical event and the electrical recognition

Position

t

p

n-1

p

n

Event received

0

1

Event

p

n-2

Œ

Delay time