0x2C02 | 0x3402 - Motor (ASM): Parameter

Subindex 7:

Motor: Rated voltage

Setting range

(min. value | unit | max. value)

Lenze setting

0

V

65535 225 V

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16

Subindex 8:

Motor: Rated cosine phi

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

655.35 0.80

Write access  CINH  OSC  P  RX  TX

Scaling: 1/100

UNSIGNED_16

Subindex 9:

Motor: Insulation class

Selection list

(Lenze setting printed in bold)

0 Y (cut-off temperature = 90°C)
1 A (cut-off temperature = 105 °C)
2 E (cut-off temperature = 120°C)
3 B (cut-off temperature = 130°C)
4 F (cut-off temperature = 155°C)
5 H (cut-off temperature = 180°C)
6 G (cut-off temperature > 180°C)

Write access  CINH  OSC  P  RX  TX

UNSIGNED_8

Subindex 10:

Motor: Designation

Write access  CINH  OSC  P  RX  TX

STRING(50)

Sub.

Name

Lenze setting

Data type

1

Motor (ASM): Rotor resistance

0.0000 Ohm

UNSIGNED_32

2

Motor (ASM): Mutual inductance

0.0 mH

UNSIGNED_32

3

Motor (ASM): Magnetising current

0.00 A

UNSIGNED_16

Subindex 1:

Motor (ASM): Rotor resistance

Setting range

(min. value | unit | max. value)

Lenze setting

0.0000

Ohm

214748.3647 0.0000 Ohm

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10000

UNSIGNED_32

Subindex 2:

Motor (ASM): Mutual inductance

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

mH

214748364.7 0.0 mH

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

UNSIGNED_32

Subindex 3:

Motor (ASM): Magnetising current

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

A

500.00 0.00 A

Write access  CINH  OSC  P  RX  TX

Scaling: 1/100

UNSIGNED_16