Parameter handling

2.2

Storage parameter set (par001.*) and total parameter set (par000.*)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

2.2

Storage parameter set (par001.*) and total parameter set (par000.*)

For the storage of the i700 servo inverter parameters, two different parameter sets are provided,

which are stored in different parameter set files in the higher-level controller:

Storage parameter set (par001.i7psf)

• Only contains the parameters of the i700 servo inverter which are writable and identified with

the "P" attribute (persistent).

• Parameters can be read out from the i700 servo inverter and saved to the file. Conversely, the

parameters stored can be written to the i700 servo inverter again.

• Recommended for storage and archiving of the controllers settings.

Total parameter set (par000.i7psf)

• Contains all parameters of the i700 servo inverter, including the mere display parameters which

vary permanently during operation.

• The total parameter set can only be read from the i700 servo inverter.
• Use for purposes of service and diagnostics.

The structure of the parameter set file is described in the appendix.

Structure of the parameter set file