3communication with the controller – Lenze i700 User Manual

Page 23

Advertising
background image

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

23

3

Communication with the controller

3.1

Acceleration of the system (initialisation)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Note!

If no data for the initialisation of the controller are transmitted, the i700 servo inverter

uses the "Lenze setting" for the parameters.

Power up/Power down
In the case of "Power up" and "Power down", no undefined states can occur that cause

damage to the device or motor movements which are not requested or not braked.
In the case of a voltage failure/dip, there is no immediate response by the i700 servo

inverter. The functionality is to be maintained for as long as possible.

24-V supply voltage monitoring

( 235)

Persistent data storage
A complete, persistent storage of the drive configuration which remains the same even

though the controller is switched off from time to time is carried out in the higher-level

controller instead of in the i700 servo inverter. Hence, the controller needs to transmit

the configuration data again to the i700 servo inverter after a power up.
However, in the case of a power down, the following device data are stored persistently

in the i700 servo inverter:

• Power-on and elapsed-hour meter (

0x2D81

or

0x3581

for axis B)

History buffer

( 265)

Advertising