Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

101

5

Motor control & motor settings

5.10

Synchronous motor (SM): Pole position identification

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

0x2C62 | 0x3462 - Pole position identification PPI (min. movement)

Sub.

Name

Lenze setting

Data type

1

PPI (min. movement): Current amplitude

25 %

UNSIGNED_16

2

PPI (min. movement): Ramp time - current

10 s

UNSIGNED_16

3

PPI (min. movement): Gain

0 %

UNSIGNED_16

4

PPI (min. movement): Reset time

62.5 ms

UNSIGNED_16

5

PPI (min. movement): Max. move permitted

20 °

UNSIGNED_8

6

PPI (min. movement): Absolute current

amplitude

UNSIGNED_32

Subindex 1:

PPI (min. movement): Current amplitude

Adjustment of the current amplitude in percent

• For large machines and high mass inertia values or for linear direct drives, the current amplitude usually has to

be increased.

• A Lenze setting of "100 %" corresponds to 35 % of the rated motor current (

0x6075

or

0x6875

for axis B).

Note!

If the current amplitude is set to > 400 %, the device utilisation (Ixt) monitoring and/or one of the motor monitoring

functions may respond and cause the abort of the pole position identification.
Setting range

(min. value | unit | max. value)

Lenze setting

1

%

1000 25 %

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16

Subindex 2:

PPI (min. movement): Ramp time - current

Adjustment of the rate of rise of the current in percent
Setting range

(min. value | unit | max. value)

Lenze setting

1

s

600 10 s

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16

Subindex 3:

PPI (min. movement): Gain

Adjustment of the proportional gain of the PI controller

• With the Lenze setting "0", the PI controller works as an I-controller.

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

1000 0 %

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16

Subindex 4:

PPI (min. movement): Reset time

Adjustment of the PI controller reset time

• For this, observe the following setting details:

• In order to be able to compensate a positional variation faster, first the reset time should be reduced. If this

does not result in the desired behaviour, the proportional gain can be increased.

• Ensure that the position control does not get unstable. We therefore recommend to use an I controller.

Setting range

(min. value | unit | max. value)

Lenze setting

0.1

ms

6000.0 62.5 ms

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

UNSIGNED_16