Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

125

5

Motor control & motor settings

5.12

Fine adjustment des motor model

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.12.1.1

Example for determining the saturation characteristic

Given values:

• Rated motor current: 5 A
• Maximum motor current: 20 A
• Maximum process current: 15 A

Procedure:

1. Deactivate correction: Set all subindices of object

0x2C04

(or

0x3404

for axis B) to 100 %.

2. Use object

0x2C05

(or

0x3405

for axis B) to set the maximum current up to which the motor is

to be actuated in the process (in this example "15 A").

3. Adjust the current controller with different current setpoints by means of the manual test mode

"current pulse" and take down the corresponding settings for Vp and Tn.

• The procedure is described in the

Manual test mode "Current pulse"

chapter.

( 108)

• The current setpoints to be set for the corresponding adjustment in object

0x2835:1

(or

0x3035:1

for axis B) result from the scaling of the maximum process current to the X axis of

the saturation characteristic.

• The grid points which are required to define the saturation characteristic with a sufficient

quality varies from motor to motor and thus has to be determined individually.

• For this example, currents that are part of the grid points 5, 9, 13, and 15 have been selected,

and a measurement at rated motor current was carried out additionally:

[5-3]

Saturation characteristic: Distribution of the grid points

Rated motor current

Maximum process current (≡ 100 %)

Œ



15 A

7.5 A

3.75 A

11.25 A

12.38 A

5 A

0

6.25

12.5

18.75

25

31.25

37.5

43.75

50

56.25

62.5

68.75

75

81.25

87.5

93.75

100

0 A

I

max

[%]

Vp
Tn

[V/A]

[ms]

x2

x3

x4

x5

x6

x7

x8

x9

x10

x11

x12

x13

x14

x15

x16

x17

x1

Specifications for adjustment

Measured values

Grid point

Scaling

Current setpoint

Vp [V/A]

Tn [ms]

5

0.25 * 15 A =

3.75 A

5.2

6.5

9

0.5 * 15 A =

7.5 A

2.6

4

13

0.75 * 15 A =

11.25 A

1.4

2.5

15

0.875 * 15 A =

12.38 A

1.0

2

17

1.0 * 15 A =

15 A

0.7

1.7

Rated motor current =

5 A

3.8

5