Monitoring functions

8.4

Monitoring of the motor utilisation (I²xt)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

The speed-dependent evaluation of the permissible motor current can actually be switched off by

parameterising all 8 characteristic points to "100 %".

Stop!

Applications with standard motors
Self-ventilated standard motors are insufficiently protected at low speeds if the speed-

dependent evaluation of the permissible motor current is not effective (all characteristic

points = "100 %").
Applications with PM synchronous motors
Please check for every individual case which r.m.s. value can be used to permanently

operate the motor at standstill.
In case of some motors, a derating I1/In < 100 % is required when n1/nn = 0 %. This

serves to prevent an overload of individual motor phases as their power loss doubles

with continuous DC current load. (It is called DC current load as the field frequency

amounts to 0 Hz at standstill.)