1 manual test mode "current pulse, Manual test mode "current pulse, Test mode "current pulse – Lenze i700 User Manual

Page 108: Manual test mode "current, Pulse, 5motor control & motor settings, Stop

Advertising
background image

5

Motor control & motor settings

5.11

Setting control loops

108

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.11.1.1

Manual test mode "Current pulse"

The current controller must be adapted to the electrical characteristics of the motor – stator

resistance and stator inductance. For an experimental adjustment, the manual test mode "Current

pulse" can be used.

Functional description
In the manual "Current pulse" test mode, setpoint step-changes are applied to the current controller

input after controller enable. The step responses then either have to be recorded using the

oscilloscope and clamp-on ammeter, or by means of the i700 servo inverter oscilloscope function.

By evaluating the step responses, it is the objective to optimise the two current controller

parameters "gain" and "reset time" so that a quick current characteristic free of harmonics is

obtained. (See the following instructions.)
Motors with individual pole windings, which can feature very distinct saturation phenomena in the

stator leakage inductance, satisfactory results are possibly only achieved with a current-dependent

correction of the current controller parameters. For this purpose, a characteristic is stored in the i700

servo inverter, describing the current dependence of the stator leakage inductance and correcting

the current controller gain.

Correction of the stator leakage inductance (Lss)...

Motor phase U is supplied with a DC current, the level of which is determined via the following

equation on the left. Motor phases V and W then carry half of this DC current, respectively (negative;

from the motor).

Note!

This test mode is intended for the adjustment of the current controller in the "servo

control for synchronous motor/asynchronous motor" mode and not for the adjustment

of the Imax controller in the "V/f characteristic control (VFC)" mode!

Stop!

In the case of the synchronous motor, a jerky compensating movement occurs after

controller enable if the pole position of this movement does not correspond to the

starting angle.

Equations for calculating the DC currents in motor phases U, V, W

Axis A

Axis B

Symbol Description

Dimension unit

0x2D83:2 0x3583:2

I

phase_U

Present current in motor phase U

A

0x2D83:3 0x3583:3

I

phase_V

Present current in motor phase V

A

0x2D83:4 0x3583:4

I

phase_W

Present current in motor phase W

A

0x2835:1 0x3035:1

I

test

Setpoint current for manual test mode

%

0x6075

0x6875

I

rated

Rated motor current

A

Greyed out = read access only

I

phase_U

2 I

test

[%]

I

rated

100 %

---------------

=

I

phase_V, _W

-0.5

2 I

test

[%]

I

rated

100 %

---------------

=