Monitoring functions

8.4

Monitoring of the motor utilisation (I²xt)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

UL 508 condition 2:
With a motor load of 110 % and a motor rotating field frequency of 10 Hz, the I²xt warning has to

be output faster than with a motor rotating field frequency of 20 Hz.

• The current motor rotating field frequency is displayed in the object

0x2DDD

(or

0x35DD

for

axis B).

• A motor load of 110 % occurs if the r.m.s. value of the total motor current displayed in the object

0x2DD1:5

(or

0x35D1:5

for axis B) corresponds to 1.1 times the rated motor current (

0x6075

or

0x6875

for axis B).

This condition can be met by the following parameter setting:

UL 508 condition 3:
After mains switching and a motor load > 100 %, the I²xt warning has to be output faster than in the

same load case before mains switching.

• A motor load of > 100 % occurs if the r.m.s. value of the total motor current displayed in the

object

0x2DD1:5

(or

0x35D1:5

for axis B) is higher than the rated motor current (

0x6075

or

0x6875

for axis B).

This condition can be met by the following parameter setting:

Object

Name

Setting

Axis A

Axis B

0x2D4D:1 0x354D:1

I²xt: x1 = n01/nN (n01 ~ 0)

0 %

0x2D4D:2 0x354D:2

I²xt: y1 = i01/iN (x = n01 ~ 0)

< 100 %

0x2D4D:3 0x354D:3

I²xt: x2 = n02/nN (n02 = limit - reduced cooling)

Setting: 100 % * 20 Hz / rated motor frequency

0x2C01:5

or

0x3401:5

)

0x2D4D:4 0x354D:4

I²xt: y2 = i02/iN (x = n02 = limit - reduced cooling)

≥ 100 %

Object

Name

Setting

Axis A

Axis B

0x2D4C:4 0x354C:4

Motor utilisation (I²xt): Starting value

> 0 %