5

Motor control & motor settings

5.14

Parameterising the V/f characteristic control

140

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.14.2

Activating the voltage vector control (lmin controller)

The voltage vector control that can be activated is used if a comparatively high starting torque has

to be ensured. The voltage vector control makes sure that the motor current required is kept at

smaller speeds in the speed range.

• The voltage vector control is activated by the selection of a current setpoint.
• For the automatic calculation of the control parameters, the "Calculate Imin controller" function

is provided via object

0x2822

(or

0x3022

for axis B).

0x2B04 | 0x3304 - VFC: Voltage vector control - setpoint current

0x2B05 | 0x3305 - VFC: Voltage vector control parameter

Note!

The voltage vector control acts additively to the

voltage boost

.

• Only use one of the two "Boost" functions.

Recommendation: voltage vector control

If the voltage vector control is used, greater losses and therefore an increased heating of

the motor result from the increased current at low speeds.

Current setpoint for voltage vector control

• If "0.00 A" are set, the voltage vector control is deactivated.

• When the current setpoint is defined, provide a reserve of 20 % to prevent a motor stalling caused by sudden

additional loads.

• Example for starting torque = rated motor torque:

The current setpoint must be set to approx. 120 % of the load current.

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

A

500.00 0.00 A

Write access  CINH  OSC  P  RX  TX

Scaling: 1/100

UNSIGNED_32

Sub.

Name

Lenze setting

Data type

1

VFC: Voltage vector controller - gain

148.21 V/A

UNSIGNED_32

2

VFC: Voltage vector controller - reset time

3.77 ms

UNSIGNED_32

Subindex 1:

VFC: Voltage vector controller - gain

Gain for voltage vector control
Setting range

(min. value | unit | max. value)

Lenze setting

0.00

V/A

750.00 148.21 V/A

Write access  CINH  OSC  P  RX  TX

Scaling: 1/100

UNSIGNED_32