3communication with the controller – Lenze i700 User Manual
Page 41
Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05
41
3
Communication with the controller
3.6
Ethernet over EtherCAT (EoE)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Response
• GCI Message Qualifier (GMQ) = 0x80 = 0b10000000 = "Response"
• Length of the user data =
20 bytes of standard user data area P0 ... P4 plus
21 bytes of attached string (incl. \0 termination) = 41 bytes
GCI header
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
GMT
GSV
GMQ
GTI
SIZE
SIZE
res
res
0x01
0x82
0x80
0x01
0x29
0x00
0x00
0x00
Fixed
Read
parameters
Response
Transactions ID
Length of the user data = 41 bytes
Reserved
User data area P0
Byte 1
Byte 2
Byte 3
Byte 4
Reserved
Data type
Reserved
0x00
0x00
0x0A
0x00
VISIBLE_STRING
User data area P1
User data area P2
Byte 1
Byte 2
Byte 3
Byte 4
Byte 1
Byte 2
Byte 3
Byte 4
Index
Reserved
Subindex
Reserved
0x0A
0x10
0x00
0x00
0x00
0x00
0x00
0x00
Index = 0x100A
No subindex
User data area P3
User data area P4
Byte 1
Byte 2
Byte 3
Byte 4
Byte 1
Byte 2
Byte 3
Byte 4
Reserved
Reserved
0x00
0x00
0x00
0x00
0x00
0x00
0x00
0x00
Note!
The read parameter value of data type VISIBLE_STRING (here: "1.5.0.9999 (release)")
follows subsequent to the standard user data area.