Westermo OS Management Guide

Version 4.17.0-0

in

sections 24.1.4

and

24.1.5

respectively.

24.1.2

Alarm sources

As of WeOS v4.17.0 the following alarm sources are supported:

Power failure: If the unit is equipped with redundant power feed (or redun-

dant power supply), an alarm can be triggered if one of the feeds lack input
power.

Note: if all power is lacking on all feeds, the unit is powerless and cannot
trigger alarms via SNMP traps or remote logging. To detect such a situation
remotely, the operator could poll the unit (e.g., by pinging the unit on a
regular interval). The drawback is that it is difficult to distinguish problems
in the intermediate network from problems in the monitored device.

An alternative is to use out-of-band signalling, e.g., via GPRS equipment
connected to digital-out to get an alarm notification instantly if a device
goes down.

Link alarm: It is possible to configure link alarm triggers to react when a

link goes down (and up).

Digital-In: Alarms can be triggered depending on the presence of input volt-

age/current on the Digital-In pins of the Digital I/O connector.

Temperature sensor alarms: Temperature alarm triggers can be configured

to react when the temperature rises above (or falls below) some defined
threshold.

FRNT status: The FRNT ring status trigger will react when an FRNT ring is

broken (bus mode) or healed (ring mode)

1

.

Hardware failure: Hardware alarms triggers notifies that the unit has de-

tected a hardware failure (typically if an unsupported SFP is inserted).

SHDSL/xDSL SNR Margin: On devices with SHDSL/xDSL ports, alarms can be

triggered when the SNR margin falls below some configured threshold.

Link Fault Forward (LFF): On devices with SHDSL ports, alarms can be trig-

gered when the remote SHDSL switch indicates it has link down on its Eth-
ernet port. That is, this feature can be used in topologies where an Ethernet

1

Only an FRNT focal point can determine the ring status with certainty.