Section 24.3.6, Section 24.3.7 – Westermo RedFox Series User Manual

Page 570

Advertising
background image

Westermo OS Management Guide

Version 4.17.0-0

24.3.6

Configure Alarm Condition Setting

Syntax condition <high|low>

Alternate keywords are possible:

rising and up are equivalents to high.
falling and down are equivalents to low.

Context

Alarm Trigger Configuration

context

Usage Define whether the high or low trigger state should be considered the

alarm state, while the other is considered the normal state.

Some triggers, such as link-alarm and power triggers have a static (prede-
fined) alarm condition setting. (Both link-alarm and power triggers have
condition set to low). For other triggers, the alarm condition setting is con-
figurable.

See

section 24.1.3.2

for more information.

Use ”show condition” to show the alarm condition setting for this trigger.

Default values Differs for different trigger types

24.3.7

Configure Rising and Falling Thresholds

Syntax threshold <NUM|[rising <NUM>]|[falling <NUM>]>

Context

Alarm Trigger Configuration

context

Usage Set falling and rising thresholds. The thresholds may be set to the same

value, but by using different thresholds (rising higher than falling) one can
avoid receiving multiple events when the alarm source fluctuates around
the alarm threshold.

Triggers which are binary to their nature, such as link-alarm, power, and
digital-in triggers have implicit thresholds, which cannot be configured.

See

section 24.1.3.2

for more information.

Use command ”show threshold” to show the trigger threshold setting (both
rising and falling thresholds) for this trigger.

Default values rising 0 and falling 0 (except for binary alarm sources)

570