Section 40.2.7, Section 40.2.6, Section 40.2.8 – Westermo RedFox Series User Manual

Page 938

Advertising
background image

Westermo OS Management Guide

Version 4.17.0-0

40.2.6

Setting ASCII Timeout

Syntax [no] ascii-timeout <MILLISECONDS>

Context modbus context

Usage Set ASCII Timeout, i.e., the maximum time between two frames in ASCII

mode. Allowed range is <10-7050> (milliseconds).

Use ”no ascii-timeout” to reset the timeout to the default value.

The ”ascii-timeout” command is only applicable when configuring the
Modbus Gateway to use ”ascii” as serial protocol (see

section 40.2.4

).

Default values 1000

Error messages None defined yet.

40.2.7

Setting RTU Interval

Syntax [no] rtu-interval <MILLISECONDS>

Context modbus context

Usage Set RTU Interval, i.e., the minimum time between two frames in RTU

mode. Allowed range is <10-7050> (milliseconds).

Use ”no rtu-interval” to reset the timeout to the default value.

The ”rtu-interval” command is only applicable when configuring the Mod-
bus Gateway to use ”rtu” as serial protocol (see

section 40.2.4

).

Default values 50

Error messages None defined yet.

40.2.8

Setting Poll Interval

Syntax [no] poll-interval <MILLISECONDS>

Context modbus context (server mode only)

Usage Set Poll Interval. Allowed values are in range <10-65535> (milliseconds).

938

➞ 2015 Westermo Teleindustri AB

Advertising
This manual is related to the following products: