Section 40.2.3, Section 40.2.4, Section 40.2.5 – Westermo RedFox Series User Manual

Page 937

Advertising
background image

Westermo OS Management Guide

Version 4.17.0-0

40.2.3

Setting Serial Port

Syntax [no] port <SERIAL-PORT>

Context modbus context

Usage Set serial port, e.g., use ”port 1” to select serial port 1 on a single slot

unit, or ”port 1/1” to select serial port 1 in slot 1 of a slotted WeOS unit.

You can use the ”show serial” command in Admin Exec (see

section 38.3.11

)

mode to list information your serial ports, including the serial port numbers.

Default values Disabled (”no port”)

Error messages None defined yet.

40.2.4

Setting Serial Protocol

Syntax [no] serial-protocol <rtu|ascii>

Context modbus context

Usage Set Serial protocol (RTU or ASCII).

Default values rtu

Error messages None defined yet.

40.2.5

Setting listen interface and port

Syntax [no] listen <IFNAME> [port <PORT>]

Context modbus context (server mode only)

Usage Setting local interface and TCP port to listen to. Acceptable port range

is in range <0-65335>, where ”port 0” results in using the default port
number (502).

Only applicable when configuring the Modbus Gateway in ”server” mode
(see

section 40.2.2

).

Default values Disabled (”no listen”) When enabled, the default port is 502.

Error messages None defined yet.

➞ 2015 Westermo Teleindustri AB

937