Memobus/modbus termination – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 106

Advertising
background image

Table 3.15 Parameter H4-07 and H4-08 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H4-07

Terminal AM signal level selection

0: 0 to 10 Vdc

1: -10 to 10 Vdc

2: 4 to 20 mA

0 to 2

0

H4-08

Terminal FM signal level selection

u

MEMOBUS/Modbus Termination

This drive is equipped with a built-in termination resistor for the RS-422/RS-485 communication connector. DIP switch S2

enables or disabled the termination resistor as shown in

Table 3.16

. The OFF position is the default. The termination resistor

should be placed to the ON position when the drive is the last in a series of slave drives.

Refer to Switches and Jumpers on

the Terminal Board on page 104

to locate switch S2.

Table 3.16 MEMOBUS/Modbus Termination Switch S2 Settings

S2 Position

Description

ON

Internal termination resistor ON

OFF

Internal termination resistor OFF (default setting)

3.6 Bypass and Drive Control I/O Connections

106

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual