Memobus/modbus termination – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 106

Table 3.15 Parameter H4-07 and H4-08 Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H4-07
Terminal AM signal level selection
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
0 to 2
0
H4-08
Terminal FM signal level selection
u
MEMOBUS/Modbus Termination
This drive is equipped with a built-in termination resistor for the RS-422/RS-485 communication connector. DIP switch S2
enables or disabled the termination resistor as shown in
. The OFF position is the default. The termination resistor
should be placed to the ON position when the drive is the last in a series of slave drives.
Refer to Switches and Jumpers on
the Terminal Board on page 104
to locate switch S2.
Table 3.16 MEMOBUS/Modbus Termination Switch S2 Settings
S2 Position
Description
ON
Internal termination resistor ON
OFF
Internal termination resistor OFF (default setting)
3.6 Bypass and Drive Control I/O Connections
106
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual