6.7 Auto-Tuning Fault Detection

Auto-Tuning faults in this section are displayed on the digital operator and will cause the motor to coast to a stop. Auto-Tuning

faults do not trigger a multi-function digital output set for fault or alarm output.
An Endo error on the digital operator display indicates Auto-Tuning has successfully completed with discrepancies in the

calculations. Restart Auto-Tuning after fixing the cause of the Endo error.
The drive may be used in the application if no cause can be identified despite the existence of an Endo error.
An Ero error indicates that Auto-Tuning has not completed successfully. Check for the cause of the error using the tables in

this section, and perform Auto-Tuning again after fixing the cause.

u

Auto-Tuning Codes, Causes, and Possible Solutions

Table 6.11 Auto-Tuning Codes, Causes, and Possible Solutions

HOA Keypad Display

Error Name

End3

Rated Current Setting Alarm (displayed after Auto-Tuning is complete)

Cause

Possible Solutions

The correct current rating printed on the motor

nameplate was not entered into T1-04

• Check the setting of parameter T1-04.
• Check the motor data and repeat Auto-Tuning.

HOA Keypad Display

Error Name

End4

Adjusted Slip Calculation Error

Cause

Possible Solutions

The calculated slip is outside the allowable range Make sure the data entered for Auto-Tuning is correct.

HOA Keypad Display

Error Name

End5

Resistance Tuning Error

Cause

Possible Solutions

The calculated resistance value is outside the

allowable range

• Double-check the data entered for the Auto-Tuning process.
• Check the motor and motor cable connection for faults.

HOA Keypad Display

Error Name

End7

No-Load Current Alarm

Cause

Possible Solutions

The entered no-load current value was outside the

allowable range

Check and correct faulty motor wiring.

Auto-Tuning results were less than 5% of the

motor rated current

Double-check the data entered for the Auto-Tuning process.

HOA Keypad Display

Error Name

Er-01

Motor Data Error

Cause

Possible Solutions

Motor data or data entered during Auto-Tuning

was incorrect

• Make sure motor data entered to T1-oo match motor nameplate information.
• Restart Auto-Tuning and enter the correct information.

Motor output power and motor-rated current

settings (T1-02 and T1-04) do not match

• Check the drive and motor capacities.
• Correct the settings of parameters T1-02 and T1-04.

Motor rated current and detected no-load current

are inconsistent

• Check the motor rated current and no-load current.
• Correct the settings of parameters T1-04 and E2-03.

Base frequency and motor rated speed (T1-05 and

T1-07) do not match

• Correct the settings of parameters T1-05 and T1-07.
• Check that the correct number of poles were entered to T1-06.

6.7 Auto-Tuning Fault Detection

262

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual