U2: fault trace – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 344

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U1-18

(0061)

oPE Fault Parameter

OPE Error Code

Displays the parameter number that caused the oPEoo or Err

(EEPROM write error) error.

No signal output

available

U1-25

(004D)

Software Number

(Flash)

CPU 1 SW Number

FLASH ID

No signal output

available

U1-26

(005B) Software No. (ROM)

CPU 2 SW Number

ROM ID

No signal output

available

U1-54

(1083)

Drive Input Power

Voltage Effective Value PowerSupply Volt

Displays the effective value of the drive input power voltage.

200 V class

10 V: 400 V

400 V class

10 V: 800 V

1 V

U1-58

(1087)

Power Supply

Frequency

PoweSupply Freq

Displays the frequency of the drive input power supply.

10 V: Rated

frequency

0.1 Hz

U1-72

(1095)

Input Power Supply

Information

Power Supply Sts

Displays information on the input power supply.

U1 - 72=

00000000

Bit 0: AUv reset. (0: Not completed, 1: Reset)
Bit 1: PF reset (0: Not completed, 1: Reset)
Bit 2: Rated frequency detection
(0: Not completed, 1: Completed)
Bit 3: Phase order detection
(0: Not completed, 1: Completed)
Bit 4: Power supply established
(0: Not completed, 1: Completed)
Bit 5: Fdv detection (0: Not detected, 1: Detected)
Bit 6: PF detection (0: Not detected, 1: Detected)
Bit 7: Reserved.

No signal output

available

<1> Display is in the following units based on drive model:

2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units

<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 208 V models. Double the value for 480 V models.
<4> Display is in the following units based on drive model:

2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 kW units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 kW units

u

U2: Fault Trace

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U2-01

(0080)

Current Fault

Current Fault

Displays the current fault.

Refer to Fault Trace Contents on page 408

for details.

No signal output

available

U2-02

(0081)

Previous Fault

Last Fault

Displays the previous fault.

No signal output

available

U2-03

(0082)

Frequency Reference at

Previous Fault

Frequency Ref

Displays the frequency reference at the previous fault.

No signal output

available

0.01 Hz

U2-04

(0083)

Output Frequency at

Previous Fault

Output Freq

Displays the output frequency at the previous fault.

No signal output

available

0.01 Hz

U2-05

(0084)

Output Current at

Previous Fault

Output Current

Displays the output current at the previous fault.

No signal output

available

<1>

<2>

U2-07

(0086)

Output Voltage at

Previous Fault

Output Voltage

Displays the output voltage at the previous fault.

No signal output

available

0.1 Vac

U2-08

(0087)

DC Bus Voltage at

Previous Fault

DC Bus Voltage

Displays the DC bus voltage at the previous fault.

No signal output

available

1 Vdc

U2-09

(0088)

Output Power at

Previous Fault

Output kWatts

Displays the output power at the previous fault.

No signal output

available

0.1 kW

U2-11

(008A)

Input Terminal Status at

Previous Fault

Input Term Sts

Displays the input terminal status at the previous fault. Displayed

as in U1-10.

No signal output

available

U2-12

(008B)

Output Terminal Status

at Previous Fault

Output Term Sts

Displays the output status at the previous fault. Displays the same

status displayed in U1-11.

No signal output

available

U2-13

(008C)

Drive Operation Status

at Previous Fault

Inverter Status

Displays the operation status of the drive at the previous fault.

Displays the same status displayed in U1-12.

No signal output

available

B.14 U: Monitors

344

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual