HOA Keypad Display

Fault Name

The option card is not properly connected to the

drive

• The connector pins on the option card do not line up properly with the connector pins on the drive.
• Reinstall the option card.

HOA Keypad Display

Fault Name

CE

MEMOBUS/Modbus Communication Error
Control data was not received for the CE detection time set to H5-09.

Cause

Possible Solution

Faulty communications wiring or an existing short

circuit

• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.

Communication data error occurred due to noise

• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or

the drive input power side.

• Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors

if required.

• Separate all communication wiring from drive power lines.

HOA Keypad Display

Fault Name

CoF

Current Offset Fault

Cause

Possible Solution

The drive tried to adjust the current offset value

beyond the allowable range. This is due to residual

induction current in the motor (e.g., during sudden

deceleration or when coasting) when the drive

attempted to start the motor.

• Create a motor restart sequence that allows enough time for residual induction voltage to dissipate.
• Enable Speed Search at start (b3-01 = 1). Use the multi-function terminals to execute External

Speed Search 1 and 2 (H1-oo = 61 or 62).

The current sensor in the drive is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

CPF00 to CPF03, CPF07, CPF08, CPF11 to

CPF14, CPF16 to CPF24

CPF26 to CPF35

CPF40 to CPF45

Control Circuit Error

Cause

Possible Solution

Hardware is damaged.

• Cycle power to the drive.
• If the problem continues, replace either the bypass control board or the entire drive. For instructions

on replacing the control board, contact Yaskawa or your nearest sales representative.

Connector on the operator is damaged.

Replace the operator.

HOA Keypad Display

Fault Name

CPF06

EEPROM Memory Data Error
Error in the data saved to EEPROM

Cause

Possible Solution

There is an error in EEPROM control circuit

• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a

Yaskawa representative for instructions on replacing the control board.

The power supply was switched off while

parameters were being saved to the drive

Reinitialize the drive using parameter A1-03.

HOA Keypad Display

Fault Name

CPF25

Terminal Board Not Connected

Cause

Possible Solution

Terminal board is not connected correctly

Reconnect the terminal board to the connector on the drive, then cycle the power to the drive.

HOA Keypad Display

Fault Name

doH

Damping Resistor Overheat
The temperature of the built-in damping resistor exceeded the set value.

6.4 Fault Detection