L5-04: fault reset interval time, 8 l: protection functions – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 189

Advertising
background image

All major faults will cause the drive to stop. For some faults it is possible to configure the drive to attempt a restart automatically.

After the fault occurs, the drive baseblocks for L2-03 seconds. After the baseblock is removed, the drive checks if a fault

condition still exists. If no fault condition exists, the drive will attempt to restart the motor. If the restart is successful, the drive

performs a Speed Search (Regardless of the status of b3-01 "Speed Search Selection") from the set speed command and the

Auto Restart Attempts count is increased by one. Even if the restart fails, the restart count is increased by one as long as the

drive attempted to rotate the motor. The restart count will not be incremented if the restart is not attempted due to a continuing

fault condition, (i.e., an ov fault). The drive waits L5-03 seconds before attempting another restart.

No.

Name

Setting Range

Default

L5-03

Time to Continue Making Fault Restarts

0.00 to 600.0 s

180.0 s

Run

Fault

Attempts

Voltage
remains high
for a long time,
then reset (1)

Drive trips on oC,
resets (2) and tries
again but motor still
shorted, trips again.

oC condition
gone, resets (3)
and runs.

Time

L2-03

L2-03

L2-03

L5-03

Count

ov

1

2

3

oC

oC

trying each

L5-03 seconds successful

successful

try but
failed

Figure 5.46 Automatic Restart Timing Diagram

The auto restart count is reset back to 0 if any of the following occur:
• No further faults for 10 minutes after the last retry.
• The drive power is turned off (the drive must be without power long enough to let control power dissipate).
• The RESET key is pushed after the last reset attempt.
The setting of parameter L5-02 determines whether the fault output (MA-MB) will be closed during an auto restart attempt.
The setting of L5-02 can be important when using the drive with other equipment.
The following faults will allow the Auto Restart function to initiate:
• oC (Overcurrent)
• LF (Output Phase Loss)
• PF (Input Phase Loss)
• oL1 (Motor Overload)
• oL3 (Overtorque Detection 1)
• oL2 (Drive Overload)
• ov (Overvoltage)
• GF (Ground Fault)
• Uv1 (Undervoltage)
• oH1 (Heatsink Overheat)
In order for auto restart after a Uv1 fault, Momentary Power Loss Ride-thru must be enabled (L2-01= 1: “Power Loss Ridethru

Time”). Setting H2-01, H2-02 or H2-03 to 1E configures a digital output as “Restart Enabled” to signal if an impending auto

restart is possible.

n

L5-04: Fault Reset Interval Time

Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.

No.

Name

Setting Range

Default

L5-04

Fault Reset Interval Time

0.5 to 600.0 s

10.0 s

5.8 L: Protection Functions

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

189

5

Programming