8 diagnosing and resetting faults, Digital operator jvop-183 – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 265

Advertising
background image

After the Fault Occurs

Procedure

Fix the cause of the fault, restart the drive, and

reset the fault

Press

on the HOA keypad.

F2

F1

ESC

M

M

AUTO

OFF

ENTER

RESET

-DRIVE-

U1- 01=60.00Hz

----------------

U1- 02=60.00Hz

JOG FWD FWD/REV

-Rdy-

ALM

DIGITAL OPERATOR JVOP-183

HAND

Freq Ref (OPR)

Resetting via Fault Reset Digital Input DI-oo

Resetting via Fault Reset serial command.

Close then open the fault signal digital input via the

digital input defined as Fault Reset (one of Z2-01

through Z2-08 set to 34).

Fault Reset Switch

Drive

DI- Fault Reset Digital Input

IG24 24V Common Digital Input Common

Turn off the main power supply if the above methods do not reset the fault. Reapply power after the

HOA keypad display has turned off.

When an “SC” error occurs, contact Yaskawa or a Yaskawa agent before cycling the power to the drive.

ON

OFF

2

1

Note:

If the Run command is present, the drive will disregard any attempts to reset the fault. Remove the Run command or press “OFF” on the

HOA keypad before attempting to clear a fault situation.

6.8 Diagnosing and Resetting Faults

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

265

6

Diagnostics & Troubleshooting