L3-03: Stall Prevention Limit during Acceleration

The Stall Prevention level is automatically reduced when the motor is operated in the constant power range. L3-03 sets the

lower limit for this reduction as a percentage of the drive rated current.

No.

Name

Setting Range

Default

L3-03

Stall Prevention Limit during Acceleration

0 to 100%

50%

Stall Prevention level during Acceleration

Output frequency

L3-03

E1-06

Base frequency

L3-02

Figure 5.41 Stall Prevention Level and Limit During Acceleration

n

L3-04: Stall Prevention Selection during Deceleration

Stall prevention during deceleration prevents the motor from stalling when a large load is imposed on the motor or rapid

deceleration is performed.

No.

Name

Setting Range

Default

L3-04

Stall Prevention Selection During Deceleration

0, 1, 4, 6

1

Setting 0: Disabled

The drive decelerates according to the set deceleration time. High inertia loads or rapid deceleration may trigger an overcurrent

(oC) fault. Switch to another L3-04 selection if an oC fault occurs.

Setting 1: General-purpose Stall Prevention

The drive tries to decelerate within the set deceleration time. The drive pauses deceleration when the output current exceeds

the Stall Prevention level and then continues deceleration when the output current drops below that level. Stall Prevention

may be triggered repeatedly to avoid an overcurrent (oC) fault.

Figure 5.42

illustrates the function of Stall Prevention during deceleration.

Output Frequency

Deceleration characteristics
when Stall Prevention was
triggered during deceleration

Time

specified deceleration time

Figure 5.42 Stall Prevention During Deceleration

Setting 4: Overexcitation Deceleration

Overexcitation Deceleration (increasing the motor flux) is faster than deceleration with no Stall Prevention (L3-04 = 0). Setting

4 changes the selected decel time and functions to provide protection from an overvoltage trip.

Setting 6: Enable (Current Limit)

The deceleration rate is automatically adjusted during deceleration of the load while limiting the regeneration current at the

setting value of the stall prevention level during deceleration (L3-14).
The stall prevention level may be reached if an external force is applied in the regeneration direction, dramatically decreasing

the possibility of stopping the motor.

5.8 L: Protection Functions

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

185

5

Programming