6.4 Fault Detection

u

Fault Displays, Causes, and Possible Solutions

Faults are detected for drive protection, and cause the drive to stop while triggering the fault output terminal MA-MB-MC.

Remove the cause of the fault and manually clear the fault before attempting to run the drive again.

Table 6.8 Detailed Fault Displays, Causes, and Possible Solutions

HOA Keypad Display

Fault Name

Aov

Power Supply Overvoltage
The input power supply voltage became equal to or higher than the Input Power Supply Overvoltage

Detection Level.

200 V Class: Approximately 277 Vrms

400 V Class: Approximately 630 Vrms

Cause

Possible Solution

• The power supply voltage exceeded the range

listed in drive input power specifications.

• Regenerative operation was performed when the

power supply capacity was too small.

• The power supply circuit opened during

regeneration.

• Reduce the voltage to within the range in the power supply specifications.
• Increase the capacity of the power supply.

HOA Keypad Display

Fault Name

AUv

Power Supply Undervoltage
The input power supply voltage became equal to or lower than the Input Power Supply Undervoltage

Detection Level (L2-21).

200 V Class: Approximately 150 Vrms

400 V Class: Approximately 300 Vrms

Cause

Possible Solution

The capacity of the power supply is too small.

Increase the capacity of the power supply.

The distortion in the power supply is too large.

Lower the impedance of the input power supply wiring.

A phase loss occurred in the input power supply. Check the input power supply for phase loss or an imbalance in the interphase voltages. Investigate

and correct the cause and then reset the fault.

The built-in fuse is open.

An internal transistor was destroyed. The input wiring is grounded or short circuited.

The output transistor has failed because the drive output has grounded or short circuited.

Replace the board or the drive. For instructions on replacing the control board, contact Yaskawa or

your nearest sales representative.

HOA Keypad Display

Fault Name

bAT

HOA Keypad Battery Voltage Low

Cause

Possible Solution

The HOA keypad battery is low

Replace the HOA keypad battery.

HOA Keypad Display

Fault Name

bUS

Option Communication Error
• The connection was lost after establishing initial communication.
• Only detected when the run command frequency reference is assigned to an option card.

Cause

Possible Solution

No signal was received from the PLC

• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.

Faulty communications wiring or an existing short

circuit

Communication data error occurred due to noise

• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Ensure that other equipment such as switches or relays do not cause noise. Use surge absorbers if

necessary.

• Use only recommended cables or other shielded line. Ground the shield on the controller side or

the drive input power side.

• Separate all communication wiring from drive power lines.

The option card is damaged

Replace the option card if there are no problems with the wiring and the error continues to occur.

6.4 Fault Detection

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

235

6

Diagnostics & Troubleshooting