C.9 BACnet Protocol Implementation Conformance Statement

Date: 9/19/2011
Vendor Name: Yaskawa America, Inc.
Product Name: VFD Bypass
Product Model Number: UTC00046X
Application Software Version: VST80029x / Firmware Revision: 1.0 / BACnet Protocol Revision: 4
Product Description:
The Yaskawa VFD Bypass is a high performance product specifically designed for commercial building automation

applications. The Yaskawa BACnet feature connects the VFD Bypass to a standard BACnet MS/TP network. These products

may be fully controlled and monitored over BACnet. All Bypass and drive parameters are available for reading and writing.
BACnet Standardized Device Profile (Annex L):
□ BACnet Operator Workstation (B-OWS)
□ BACnet Building Controller (B-BC)
□ BACnet Advanced Application Controller (B-AAC)
■ BACnet Application Specific Controller (B-ASC)
□ BACnet Smart Sensor (B-SS)
□ BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building Blocks Supported (Annex K):
• Data Sharing-ReadProperty-B (DS-RP-B)
• Data Sharing-WriteProperty-B (DS-WP-B
• Device Management-Dynamic Device Binding-B (DM-DDB-B)
• Device Management-Dynamic Object Binding-B (DM-DOB-B)
• Device Management-DeviceCommunicationControl-B (DM-DCC-B)
• Device Management-ReinitializeDevice-B (DM-RD-B)
• Device Management-TimeSyncronization-B (DM-TS-B)
Segmentation Capability:
□ Segmented requests supported / Window Size
□ Segmented responses supported / Window Size
Standard Object Types Supported:
• Device Object
• Analog Input Object
• Analog Output Object
• Analog Value Object
• Binary Input Object
• Binary Output Object
• Binary Value Object
Data Link Layer Options:
□BACnet IP, (Annex J)
□BACnet IP, (Annex J), Foreign Device
□ISO 8802-3, Ethernet (Clause 7)
□ ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
□ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
■MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800
□MS/TP slave (Clause 9), baud rate(s):
□Point-To-Point, EIA 232 (Clause 10), baud rate(s):
□Point-To-Point, modem, (Clause 10), baud rate(s):

C.9 BACnet Protocol Implementation Conformance Statement