Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 245

Advertising
background image

HOA Keypad Display

Fault Name

oFC02

Option Card Fault at Option Port CN5-C
Same type of option card is currently connected

Cause

Possible Solution

An option card of the same type is already installed

in option port CN5-A or CN5-B.

Only one of each option card type can only be installed simultaneously. Make sure only one type of

option card is connected.

An input option card is already installed in option

port CN5-A or CN5-B.

Install a communication option, a digital input option, or an analog input option. More than one of

the same type of card cannot be installed simultaneously.

HOA Keypad Display

Fault Name

oFC03 to oFC11

Option Card Error Occurred at Option Port CN5-C

oFC12 to oFC17

Cause

Possible Solution

Option card or hardware is damaged

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a

Yaskawa representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

oFC50 to oFC55

Option Card Error Occurred at Option Port CN5-C

Cause

Possible Solution

Option card or hardware is damaged

Refer to the option manual for details.

HOA Keypad Display

Fault Name

oH

Heatsink Overheat
The heatsink temperature exceeded the overheat pre-alarm level set to L8-02. The default value for

L8-02 is determined by drive capacity (o2-04).

Cause

Possible Solution

Surrounding temperature is too high

• Check the temperature surrounding the drive. Verify temperature is within drive specifications.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy

• Measure the output current.
• Decrease the load.
• Lower the carrier frequency (C6-02).

External cooling fan is stopped

• Replace the cooling fan.

Refer to Cooling Fan Replacement: 2

o0028 to 2o0130 and 4o0011

to 4

o0124 on page 287

.

• After replacing the cooling fan, set parameter o4-03 to 0 to reset the cooling fan maintenance.

HOA Keypad Display

Fault Name

oH1

Overheat 1 (Heatsink Overheat)
The heatsink temperature exceeded the drive overheat level. Overheat level is determined by drive

capacity (o2-04).

Cause

Possible Solution

Surrounding temperature is too high

• Check the temperature surrounding the drive.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy

• Measure the output current.
• Lower the carrier frequency (C6-02).
• Reduce the load.

HOA Keypad Display

Fault Name

oH3

Motor Overheat Alarm (PTC Input)
• The motor overheat signal to analog input terminals A1, A2, or A3 exceeded the alarm detection

level.

• Detection requires setting multi-function analog inputs H3-02, H3-06, or H3-10 to E.

Cause

Possible Solution

6.4 Fault Detection

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

245

6

Diagnostics & Troubleshooting