4.6 Auto-Tuning

u

Types of Auto-Tuning

Refer to

Table 4.14

to select the type of Auto-Tuning that bests suits the application.

n

Auto-Tuning for Induction Motors

This feature automatically sets the V/f pattern and motor parameters E1-oo and E2-oo for an induction motor.

Table 4.14 Types of Auto-Tuning for Induction Motors

Type

Setting

Application Conditions and Benefits

Control

Mode

V/f

Stationary Auto-Tuning for Line-

to-Line Resistance

T1-01 = 2

• The drive is used in V/f Control and other Auto-Tuning selections are not

possible.

• Drive and motor capacities differ.
• Tunes the drive after the cable between the drive and motor has been replaced

with a cable over 50 m long. Assumes Auto-Tuning has already been

performed.

• Should not be used for any vector control modes unless the motor cable has

changed.

YES

Rotational Auto-Tuning for V/f

Control

T1-01 = 3

• Recommended for applications using Speed Estimation Speed Search or using

the Energy Saving function in

V/f Control.

• Assumes motor can rotate while Auto-Tuning is executed. Increases accuracy

for certain functions like torque compensation, slip compensation, Energy

Saving, and Speed Search.

YES

Table 4.15

lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting Auto-Tuning.

The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor

manufacturer.

Table 4.15 Auto-Tuning Input Data

Input Value

Input Parameter

Unit

Tuning Type (T1-01)

2

Line-to-Line Resistance

3

Rotational for

V/f Control

Motor rated power

T1-02

kW

YES

YES

Motor rated voltage

T1-03

Vac

YES

Motor rated current

T1-04

A

YES

YES

Motor rated frequency

T1-05

Hz

YES

Number of motor poles

T1-06

-

YES

Motor rated Speed

T1-07

r/min

YES

Motor iron loss

T1-11

W

YES

u

Before Auto-Tuning the Drive

Check the items below before Auto-Tuning the drive.

n

Basic Auto-Tuning Preparations

• Auto-Tuning requires the user to input data from the motor nameplate or motor test report. Make sure this data is available

before Auto-Tuning the drive.

• For best performance, the drive input supply voltage must be at least equal to or greater than the motor rated voltage.

Note:

Better performance is possible when using a motor with a base voltage that is lower than the input supply voltage (20 V for 208 V models

and 40 V for 480 V models). This is particularly important when operating the motor above 90% of base speed, where high torque precision

is required.

• To cancel Auto-Tuning, press the OFF key on the HOA keypad.
• When using a motor contactor, make sure it is closed throughout the Auto-Tuning process.

4.6 Auto-Tuning

126

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual