Fault trace contents, For details, For parameter details and – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 408: Refer to fault trace

Advertising
background image

Register No.

Contents

0001H

Digital Input Command
bit 0

Forward Run (0: Stop 1: Run)

bit 1

Direction Command (0: Forward, 1: Reverse)

bit 2, 3

Reserved

bit 4

External Fault

bit 5

Fault Reset

bit 6 to B

Reserved

bit C

Multi-Function Digital Input S5

bit D

Multi-Function Digital Input S6

bit E

Multi-Function Digital Input S7

bit F

Multi-Function Digital Input S8

0002H

Frequency Reference

30000/100%

u

Fault Trace Contents

The table below shows the fault codes that can be read out by MEMOBUS/Modbus commands from the U2-oo monitor

parameters.

Table D.3 Fault Trace / History Register Contents

Fault Code

Fault Name

0002H

Control Circuit Undervoltage Fault (Uv1)

0003H

Control Power Supply Voltage Fault (Uv2)

0004H

Undervoltage 3 (Uv3)

0006H

Ground Fault (GF)

0007H

Overcurrent (oC)

0008H

Control Circuit Overvoltage (ov)

0009H

Heatsink Overheat (oH)

000AH

Overheat 1 (oH1)

000BH

Motor Overload (oL1)

000CH

Overload (oL2)

000DH

Overtorque Detection 1 (oL3)

000EH

Overtorque Detection 2 (oL4)

0011H

External Fault at Input Terminal S3 (EF3)

0012H

External Fault at Input Terminal S4 (EF4)

0013H

External Fault at Input Terminal S5 (EF5)

0014H

External Fault at Input Terminal S6 (EF6)

0015H

External Fault at Input Terminal S7 (EF7)

0016H

External Fault at Input Terminal S8 (EF8)

0017H

Fan Fault (FAn)

0018H

Overspeed (oS)

0019H

Speed Deviation (dEv)

001AH

PG Disconnect (PGo)

001CH

Output Phase Loss (LF)

001DH

Motor Overheat Alarm (PTC input) (oH3)

001EH

Digital Operator Connection Fault (oPr)

001FH

EEPROM Write Error (Err)

0020H

Motor Overheat Fault (PTC input) (oH4)

0021H

MEMOBUS/Modbus Communication Error (CE)

0022H

Option Communication Error (bUS)

0025H

Control Fault (CF)

0026H

Zero-Servo Fault (SvE)

0027H

Option Card External Fault (EF0)

Fault Code

Fault Name

0028H

PID Feedback Loss (FbL)

0029H

Undertorque Detection 1 (UL3)

002AH

Undertorque Detection 2 (UL4)

0030H

Hardware Fault (including oFx)

0032H

Z Pulse Fault (dv1)

0033H

Z Pulse Noise Fault Detection (dv2)

0034H

Inversion Detection (dv3)

0035H

Inversion Prevention Detection (dv4)

0036H

Output Current Imbalance (LF2)

0037H

Pull-Out Detection (Sto)

0038H

PG Hardware Fault (PGoH)

0039H

MECHATROLINK Watchdog Timer Error (E5)

003BH

Too Many Speed Search Restarts (SEr)

0041H

Excessive PID Feedback (FbH)

0042H

External Fault 1, Input Terminal S1 (EF1)

0043H

External Fault 2, Input Terminal S2 (EF2)

0044H

Mechanical Weakening Detection 1 (oL5)

0045H

Mechanical Weakening Detection 2 (UL5)

0046H

Current Offset Fault (CoF)

0049H

DriveWorksEZ Fault (dWFL)

004AH

EEPROM Memory DriveWorksEZ Data Error

(dWF1)

0051H

LSo Fault (LSo)

0052H

CanOpenNID Error (nSE)

005BH

Initial Polarity Estimation Timeout (dv7)

005CH

Ground Fault (GF)

005FH

Power Unit Output Phase Loss 3 (LF3)

0066H

Power Supply Undervoltage (AUv)

0067H

Power Supply Overvoltage (Aov)

0068H

Power Supply Frequency Fault Detection (Fdv)

0069H

Phase Order Detection Fault (SrC)

0081H

Control Circuit Error (CPF00)