Wiring diagram for multiple connections, Network termination, Rs-485 interface – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 434: F.2 connecting to a network

Advertising
background image

u

Wiring Diagram for Multiple Connections

Figure F.3

explains the wiring diagrams for multiple connections using N2 communication.

n

RS-485 Interface

CONTROLLER

(customer-supplied)

1

2

3

4

+

-

SHLD

Bypass Drive

S1

OFF

TB3

SHLD

TXRX-

TXRX+

IG5

1

2

3

4

Bypass Drive

S1

OFF

TB3

SHLD

TXRX-

TXRX+

IG5

ON

1

2

3

4

Bypass Drive

S1

SHLD

TXRX-

TXRX+

IG5

Bypass
Control
Board A2

Bypass
Control
Board A2

Bypass
Control
Board A2

TB3

COMMON

Figure F.3 Connection Diagram for Multiple Connections

Note:

Turn on DIP switch S1 on the bypass that is located at the end of the network. If S1 is missing, then an external 120 ohm resistor must be

placed across terminals TXRX+ and TXRX-. All other slave devices must have this DIP switch set to the OFF position (or if S1 is missing,

no external resistor is used).

u

Network Termination

The two ends of the network line must be terminated with a 120 ohm resistor between the TXRX+ and TXRX- signals. The

bypass has a built in termination resistor that can be enabled or disabled using DIP switch S1. If a bypass is located at the end

of a network line, enable the termination resistor by setting DIP switch S1 to the ON position. Disable the termination resistor

on all slaves that are not located at the network line end.

Note:

Some bypass controllers do not have DIP switch S1. in such cases an external 120 ohm resistor must be placed across the

TXRX+ and TXRX- signals if the bypass controller is at the end of a network line.

F.2 Connecting to a Network

434

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising