5.5 E: Motor Parameters

E parameters cover V/f pattern and motor data settings.

u

E1: V/f Pattern for Motor 1

n

V/f Pattern Settings (E1-03)

The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference. There are 15 different predefined

V/f patterns (setting 0 to E) from which to select, each with varying voltage profiles, saturation levels (frequency at which

maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern is available (setting F) that

requires the user to create the pattern using parameters E1-04 through E1-10.

n

E1-03: V/f Pattern Selection

Selects the V/f pattern for the drive and motor from 15 predefined patterns or creates a custom V/f pattern.

No.

Parameter Name

Setting Range

Default

E1-03

V/f Pattern Selection

0 to 9; A to F

F

Setting a Predefined V/f Pattern (Setting 0 to F)

Choose the V/f pattern that best meets the application demands from the table below. Set the correct value to E1-03. Parameter

E1-05 can only be monitored, not changed.

Note:

1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Drive initialization does not reset parameter E1-03.

Table 5.8 Predefined V/f Patterns

Setting

Specification

Characteristic

Application

0

50 Hz

Constant torque

For general purpose applications. Torque remains constant

regardless of changes to speed.

1

60 Hz

2

60 Hz (with 50 Hz base)

3

72 Hz (with 60 Hz base)

4

50 Hz, Variable torque 1

Variable torque

For fans, pumps, and other applications where the required

torque changes as a function of the speed.

5

50 Hz, Variable torque 2

6

50 Hz, Variable torque 3

7

50 Hz, Variable torque 4

8

50 Hz, Mid starting torque

High starting torque

Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.

9

50 Hz, High starting torque

A

60 Hz, Mid starting torque

B

60 Hz, High starting torque

C

90 Hz (with 60 Hz base)

Constant output

Output voltage is constant when operating at greater than

60 Hz.

D

120 Hz (with 60 Hz base)

E

180 Hz (with 60 Hz base)

F

<1>

60 Hz

Variable torque

Used for variable torque applications. The default setting is

the same as V/f pattern Setting 7.

<1> Setting F enables a custom V/f pattern by changing parameters E1-05. When the bypass is shipped, the default values for parameter E1-05 is are

equal to predefined V/f pattern 1.

The following tables show details on predefined V/f patterns.

5.5 E: Motor Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

159