Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 314

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-05

(01A9) Derivative Time (D)

PID D Time

Sets D control derivative time.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

146

b5-06

(01AA) PID Output Limit

PID Limit

Sets the maximum output possible from the entire PID controller

as a percentage of the maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 100.0

146

b5-07

(01AB) PID Offset Adjustment PID Offset

Applies an offset to the PID controller output. Set as a

percentage of the maximum output frequency.

Default: 0.0%

Min.: -100.0

Max.: 100.0

146

b5-08

(01AC) PID Primary Delay

Time Constant

PID Delay Time

Sets a low pass filter time constant on the output of the PID

controller.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

146

b5-09

(01AD)

PID Output Level

Selection

Output Level Sel

0: Normal Character

1: Rev Character

0: Normal output (direct acting)

1: Reverse output (reverse acting)

Default: 0

Range: 0, 1

147

b5-10

(01AE) PID Output Gain Setting Output Gain

Sets the gain applied to the PID output.

Default: 1.00

Min.: 0.00

Max.: 25.00

147

b5-11

(01AF)

PID Output Reverse

Selection

Output Rev Sel

0: 0 limit

1: Reverse

0: Negative PID output triggers zero limit.

1: Rotation direction reverses with negative PID output.

Note:

When using setting 1, make sure reverse

operation is permitted by b1-04.

Default: 0

Range: 0, 1

147

b5-12

(01B0)

PID Feedback Loss

Detection Selection

Fb loss Det Sel

0: DO Only – Always

1: Alarm – Always

2: Fault – Always

3: DO Only@PID

Enb

4: Alarm @ PID Enbl

5: Fault @ PID Enbl

0: Digital Output Only

(Remains active when PID is disabled by digital input)

1: Alarm output, drive continues operation (Remains active

when PID is disabled by digital input)

2: Fault output, drive output is shut off (Remains active when

PID is disabled by digital input)

3: Digital output only. No detection when PID is disabled by

digital input.

4: Alarm detection. No detection when PID is disabled by digital

input.

5: Fault detection. No detection when PID is disabled by digital

input.

Default: 0

Range: 0 to 5

148

b5-13

(01B1)

PID Feedback Loss

Detection Level

Fb loss Det Lvl

Sets the PID feedback loss detection level as a percentage of the

maximum output frequency.

Default: 0%

Min.: 0

Max.: 100

148

b5-14

(01B2)

PID Feedback Loss

Detection Time

Fb loss Det Time

Sets a delay time for PID feedback loss.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

148

b5-15

(01B3)

PID Sleep Function Start

Level

PID Sleep Level

Sets the frequency level that triggers the sleep/snooze function. Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

149

b5-16

(01B4) PID Sleep Delay Time

PID Sleep Time

Sets a delay time before the sleep/snooze function is triggered. Default: 0.0 s

Min.: 0.0

Max.: 25.5

149

b5-17

(01B5) PID Accel/Decel Time PID Acc/Dec Time

Sets the acceleration and deceleration time to PID setpoint.

Default: 0.0 s

Min.: 0.0

Max.: 6000.0

149

b5-18

(01DC) PID Setpoint Selection

PID Setpoint Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

150

b5-19

(01DD) PID Setpoint Value

PID Setpoint

Sets the PID target value when b5-18 = 1. Set as a percentage

of the maximum output frequency.

Default: 0.00%

Min.: 0.00
Max.: 100.00

<1>

150

b5-20

(01E2) PID Setpoint Scaling

PID Disp Scaling

0: 0.01Hz units

1: 0.01% units

2: r/min

3: User Units

0: 0.01 Hz units

1: 0.01% units (100% = max output frequency)

2: r/min (number of motor poles must entered)

3: User-set (set scaling to b5-38 and b5-39)

Default: 1

Range: 0 to 3

150

B.3 b: Application

314

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual