U: monitor parameters, Ub: bypass monitors, U1: operation status monitors – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 206: U2: fault trace, U3: fault history, U4: maintenance monitors, U5: pid monitors, U9: power monitors, 13 u: monitor parameters, Refer to u: monitor

Advertising
background image

5.13 U: Monitor Parameters

Monitor parameters let the user view various aspects of drive performance using the HOA keypad display. Some monitors

can be output from terminals FM and AM by assigning the specific monitor parameter number (Uo-oo) to H4-01 and H4-04.

Refer to H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection on page 180

for details on

assigning functions to an analog output.

u

UB: Bypass Monitors

These monitors display various aspects of bypass control.

Refer to UB: Bypass Control Monitors on page 341

for a complete

list of UB-oo monitors and descriptions.

u

U1: Operation Status Monitors

Status monitors display drive status data such as output frequency and output current.

Refer to U1: Operation Status

Monitors on page 342

for a complete list of U1-oo monitors and descriptions.

u

U2: Fault Trace

Use these monitor parameters to view the status of various drive aspects when a fault occurs.
This information is helpful for determining the cause of a fault.

Refer to U2: Fault Trace on page 344

for a complete list of

U2-oo monitors and descriptions.
U2-oo monitors are not reset when the drive is initialized.

Note:

Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.

u

U3: Fault History

These parameters display faults that have occurred during operation as well as the drive operation time when those faults

occurred.

Refer to U3: Fault History on page 345

for a complete list of U3-oo monitors and descriptions.

U3-oo monitors are not reset when the drive is initialized.

Note:

Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.

u

U4: Maintenance Monitors

Maintenance monitors show:
• Runtime data of the drive and cooling fans and number of Run commands issued
• Maintenance data and replacement information for various drive components
• kWh data
• Highest peak current that has occurred and output frequency at the time the peak current occurred
• Motor overload status information
• Detailed information about the present Run command and frequency reference source selection

Refer to U4: Maintenance Monitors on page 347

for a complete list of U4-oo monitors and descriptions.

u

U5: PID Monitors

These monitors display various aspects of PID control.

Refer to PID Block Diagram on page 145

for details on how these

monitors display PID data.

Refer to U5: PID Monitors on page 348

for a complete list of U5-oo monitors and descriptions.

u

U9: Power Monitors

The total consumed power and regenerated power are displayed for these parameters.

Refer to U9: Power Monitors on page

349

for a complete list of U9-oo monitors and descriptions.

5.13 U: Monitor Parameters

206

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising