H: terminal functions, H1: multi-function digital inputs, 7 h: terminal functions – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 165

Advertising
background image

5.7 H: Terminal Functions

H parameters assign functions to the external terminals.

u

H1: Multi-Function Digital Inputs

n

H1-03 to H1-08: Functions for Terminals S3 to S8

These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in

Table

5.21

.

No.

Parameter Name

Setting

Range

Default

H1-03

Multi-Function Digital Input Terminal S3 Function Selection

3 to 60

24: External Fault

H1-04

Multi-Function Digital Input Terminal S4 Function Selection

3 to 60

14: Fault Reset

H1-05

Multi-Function Digital Input Terminal S5 Function Selection

3 to 60

3: Multi-Step Speed Reference 1

H1-06

Multi-Function Digital Input Terminal S6 Function Selection

3 to 60

4: Multi-Step Speed Reference 2

H1-07

Multi-Function Digital Input Terminal S7 Function Selection

3 to 60

F: Not Used (Through Mode)

H1-08

Multi-Function Digital Input Terminal S8 Function Selection

3 to 60

F: Not Used (Through Mode)

Table 5.21 Multi-Function Digital Input Terminal Settings

Setting

Function

Page

3

Multi-Step Speed Reference 1

165

4

Multi-Step Speed Reference 2

6

Jog reference Selection

165

C

Analog Terminal Input Selection

165

F

Not Used (Through Mode)

165

10

Up Command

165

11

Down Command

Setting

Function

Page

14

Fault Reset

167

19

PID Disable

167

24

External Fault

167

60

Motor Pre-Heat 1

167

Settings 3 and 4: Multi-Step Speed Reference 1 and 2

Switches multi-step speed frequency references d1-01 to d1-04 by digital inputs.

Refer to d1: Frequency Reference on page

156

for details.

Setting 6: Jog Reference Selection

The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes.

Refer to d1:

Frequency Reference on page 156

for details.

Setting C: Analog Terminal Input Selection (Terminals A1 and A2)

When closed, the terminals specified in H3-14 are enabled. When open, the drive disregards the input signal to the analog

terminals.

Setting F: Not Used (Through Mode)

Select this setting when using the terminal in a pass-through mode. When set to F, an input does not trigger any function in

the drive. Setting F, however, still allows the input status to be read out by a PLC via a communication option or MEMOBUS/

Modbus communications.

Settings 10 and 11: Up/Down Function

The Up/Down function allows the frequency reference to be set by two push buttons when one digital input is programmed

as the Up input (H1-oo= 10) to increase the frequency reference and the other digital input is programmed as the Down input

(H1-oo= 11) to decrease the frequency reference.
The Up/Down function takes priority over the frequency references from the HOA keypad, the analog inputs, and the pulse

input (b1-01 = 0, 1, 4). When using the Up/Down function, references provided by these sources will be disregarded.
The inputs operate as shown in the table below:

5.7 H: Terminal Functions

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

165

5

Programming

Advertising