E2: motor 1 parameters – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 321

Advertising
background image

u

E2: Motor 1 Parameters

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

E2-01

(030E) Motor Rated Current

Motor Rated FLA

Sets the motor nameplate full load current in amps.

Automatically set during Auto-Tuning.

Default:

<1>

Min.: 10% of

drive rated

current

Max.: 150% of

drive rated
current

<2>

163

E2-03

(0310)

Motor No-Load Current No-Load Current

Sets the no-load current for the motor. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0.00 A
Max.: E2-01

<2>

163

E2-04

(0311)

Number of Motor Poles Number of Poles

Sets the number of motor poles. Automatically set during

Auto-Tuning.

Default: 4

Min.: 2

Max.: 48

E2-05

(0312)

Motor Line-to-Line

Resistance

Term Resistance

Sets the phase-to-phase motor resistance. Automatically set

during Auto-Tuning.

Default:

<1>

Min.: 0.000 Ω

Max.: 65.000 Ω

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Display is in the following units based on drive model:

2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units

B.6 E: Motor Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

321

B

Parameter List