U5: pid monitors – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 348

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U4-21

(07DD)

Run Command Source

Selection

Run Cmd Source

Displays the source for the Run command as XY-nn.

X: Indicates which Run source is used:

0 = OFF

1 = AUTO

2 = HAND

Y: Input power supply data

0 = HOA keypad

1 = External terminals

3 = Serial communications (APOGEE FLN, BACnet,

MEMOBUS/Modbus, or Metasys N2)

4 = Communication option card

nn: Run command limit status data

00: No limit status.

01: Run command was left on when stopped in the PRG mode

02: Run command was left on when switching from LOCAL to

REMOTE operation

03: Waiting for soft charge bypass contactor after power up (Uv

or Uv1 flashes after 10 s)

04: Waiting for “Run command prohibited” time period to end

05: Fast Stop (digital input, HOA keypad)

06: b1-17 (Run command given at power-up)

07: During baseblock while coast to stop with timer

08: Frequency reference is below minimal reference during

baseblock

09: Waiting for Enter command

No signal output

available

U4-22

(07DE)

MEMOBUS/Modbus

Communications

Reference

MEMOBUS Ref Reg

Displays the drive control data set by MEMOBUS/Modbus

communications register no. 0001H as a four-digit hexadecimal

number.

No signal output

available

U4-23

(07DF)

Communication Option

Card Reference

Option Ref Reg

Displays drive control data set by an option card as a four-digit

hexadecimal number.

No signal output

available

<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

u

U5: PID Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U5-01

(0057)

PID Feedback

PID Feedback 1

Displays the PID feedback value.

10 V: 100%

0.01%

U5-02

(0063)

PID Input

PID Input

Displays the amount of PID input (deviation between PID

setpoint and feedback).

10 V: 100%

0.01%

U5-03

(0064)

PID Output

PID Output

Displays PID control output.

10 V: 100%

0.01%

U5-04

(0065)

PID Setpoint

PID Setpoint

Displays the PID setpoint.

10 V: 100%

0.01%

U5-05

(07D2)

PID Differential

Feedback

PID Feedback 2

Displays the second PID feedback value if differential feedback

is used (H3-oo = 16).

10 V: 100%

0.01%

U5-06

(07D3) PID Adjusted Feedback PID Diff Fdbk

Displays the difference of both feedback values if Differential

Feedback is used (U5-01 - U5-05).

If PID Square Root Feedback or Differential Feedback are

enabled, U5-01

≠ U5-06.

If PID Square Root Feedback or Differential Feedback are NOT

enabled, U5-01= U5-06.

10 V: 100%

0.01%

U5-30

(3000)

Time Hr Min HHMM

Time Hr Min HHMM Displays the current time (Hours and Minutes).

No signal output

available

1

U5-31

(3001)

Date Year

Date Year

Displays the current year.

No signal output

available

1

U5-32

(3002)

Date Mo Day MMDD

Date Mo Day MMDD Displays the current date (Month and Day).

No signal output

available

1

B.14 U: Monitors

348

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual