C7: Voltage Adjustment

n

C7-60: Output Voltage Limit Mode Selection

Sets the mode to limit the output voltage.
Set this parameter to 0 (Harmonic suppression priority mode) to give priority to harmonic suppression. The maximum output

voltage is automatically limited to suppress harmonics.
Set this parameter to 1 (High output voltage mode) to give priority to the output voltage over harmonic suppression. The

effectiveness of harmonic suppression will be reduced because the maximum output voltage will be used.

No.

Parameter Name

Setting Range

Default

C7-60

Output Voltage Limit Mode Selection

0, 1

1

Setting 0: Harmonic Suppression Priority Mode
Setting 1: High Output Voltage Mode

5.3 C: Tuning

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

155