C7: voltage adjustment – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 155
u
C7: Voltage Adjustment
n
C7-60: Output Voltage Limit Mode Selection
Sets the mode to limit the output voltage.
Set this parameter to 0 (Harmonic suppression priority mode) to give priority to harmonic suppression. The maximum output
voltage is automatically limited to suppress harmonics.
Set this parameter to 1 (High output voltage mode) to give priority to the output voltage over harmonic suppression. The
effectiveness of harmonic suppression will be reduced because the maximum output voltage will be used.
No.
Parameter Name
Setting Range
Default
C7-60
Output Voltage Limit Mode Selection
0, 1
1
Setting 0: Harmonic Suppression Priority Mode
Setting 1: High Output Voltage Mode
5.3 C: Tuning
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
155
5
Programming