HOA Keypad Display

Fault Name

Cause

Possible Solution

The power supply phase order changed during

operation.

Investigate and correct the cause and reset the fault.

Refer to Diagnosing and Resetting Faults on

page 264

.

An input power supply wiring terminal is loose.
The fluctuation in the voltage of the input power

supply is too large.

HOA Keypad Display

Fault Name

Srr

Internal Resistance Fault
An operation failure occurred in the snubber discharge resistor circuit.

Cause

Possible Solution

The snubber discharge resistor or peripheral

circuits failed.

• Cycle power to the drive.
• If the problem continues, replace either the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or your nearest sales representative.

HOA Keypad Display

Fault Name

SvE

Zero Servo Fault
Position deviation during zero servo.

Cause

Possible Solution

Torque limit is set too low

Set the torque limit to an appropriate value using parameters L7-01 to L7-04.

Excessive load torque

Reduce the amount of load torque.

HOA Keypad Display

Fault Name

TdE

Time Data Error

Cause

Possible Solution

An error has occurred in the Real-Clock Time

function of the HOA keypad

Replace the HOA keypad. For instructions on replacing the HOA keypad, contact Yaskawa or your

nearest sales representative.

A communication error has occurred with the

Real-Clock Time function of the HOA keypad

HOA Keypad Display

Fault Name

TIM

Time Not Set

Cause

Possible Solution

The Real-Time Clock for the HOA keypad is not

set in parameter o4-17
• The drive is a new drive, first power-up

condition

• o4-17 was set to (2: Reset), by the user, manually

clearing the Real-Time Clock data.

Set the time for the HOA keypad. Parameter o4-17 = 1.

The drive will display the "TIM" alarm (Time Not Set) whenever the Real time Clock is not set .

Additionally, at power up, if the "TIM" condition is present, the drive will automatically switch to

the time setting screen (o4-17 = 1) for 30 seconds to prompt the user to set the Real-Time Clock.

The user did not set the Real Time Clock when

prompted following power-up.

Cycle power to the drive and set the Real Time Clock within 30 seconds of power-up, or set the clock

manually via parameter o4-17.

The HOA keypad battery is low or the battery has

been replaced

Replace the HOA keypad battery and set the Real-Time Clock.

An error has occurred in the Real-Time Clock

function of the HOA keypad

Replace the HOA keypad. For instructions on replacing the HOA keypad, contact Yaskawa or your

nearest sales representative.

HOA Keypad Display

Fault Name

UL3

Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the

allowable time (L6-03).

Cause

Possible Solution

Parameter settings are not appropriate for the load Check the settings of parameters L6-02 and L6-03.
There is a fault on the machine side

Check the load for any problems.

6.4 Fault Detection