Setting 0: Triggered when a Run Command Is Issued (Normal)
Setting 1: Triggered when an External Baseblock Is Released

n

b3-31: Speed Search Operation Current Level 1 (Current Detection Type 2)

Sets the current level used to limit the output current during Current Detection Type Speed Search 2 as a ratio to E2-03, Motor

No-Load Current.
The current level is determined for a no-load current that is 30% of the rated motor current when the setting value of E2-03

is less than or equal to 30% of the rated motor current.

Note:

If the setting value is too large, a stopped inductive motor may accelerate too quickly. In such cases, set this parameter to a value that is

smaller than the rated motor current.

No.

Name

Setting Range

Default

b3-31

Speed Search Operation Current Level 1 (Current Detection Type

2)

1.50 to 3.50

1.50

n

b3-32: Speed Search Operation Current Level 2 (Current Detection 2)

Sets the current level at which to end the Speed Search for Current Detection Type Speed Search 2 as a ratio to E2-03, Motor

No-Load Current.
The current level is determined for a no-load current that is 30% of the rated motor current when the setting value of E2-03

is less than or equal to 30% of the rated motor current.

No.

Name

Setting Range

Default

b3-32

Speed Search Operation Current Level 2 (Current Detection 2)

0.00 to 1.49

1.20

n

b3-33: Speed Search Selection when Run Command is Given during Uv

Activates and deactivates Speed Search at start in accordance with whether a Run command was issued during an undervoltage

(Uv) condition. Function is active when a momentary power loss (L2-01 = 1 or 2), Speed Search at start (b3-01 = 1), and

coasting to a stop (b1-03 = 1) are enabled.

No.

Name

Setting Range

Default

b3-33

Speed Search Selection when Run Command is Given during Uv

0, 1

0

Setting 0: Disabled
Setting 1: Enabled

n

b3-50/b3-51: Backspin Search Direction Judgment Time 1/2

The direction of the Speed Search is adjusted to allow for backspin.
When momentary power loss time t is shorter than the time set in b3-50, the search operates according to the direction command.

When momentary power loss time t is equal to or longer than the time set in b3-51, the search operates from the opposite

direction of the direction command. When momentary power loss time t is equal to or longer than the time set in b3-50 and

shorter than b3-15, baseblock continues until momentary power loss time t exceeds the time set in b3-51. The search then

operates from the opposite direction of the direction command.

Note:

1. Use these parameters only in applications in which backspin can occur
2. Be sure to set b3-50 > b3-51.

No.

Name

Setting Range

Default

b3-50

Backspin Search Direction Judgment Time 1

0.0 to 10.0

Determined by

A1-02

b3-51

Backspin Search Direction Judgment Time 2

0.0 to 10.0

0.0

Speed Search from the Direction Command (0.0 ≤ Momentary Power Loss Time t < b3-50)

When time t from the momentary power loss to recovery is shorter than the setting value of b3-50, Speed Search is performed

in the direction specified by the direction command. The deceleration time set in b3-52 is used for the search frequency and

the setting value of the maximum frequency is used as the starting search frequency.

5.2 b: Application

140

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual