Z1-07: speed reference select – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 208

Advertising
background image

Setting 4: HAND-BYPASS

When drive powers up , the bypass will get a "HAND” command and needs an “OFF” command to stop.

n

Z1-07: Speed Reference Select

Selects the frequency reference source 1.

Note:

If a Run command is input to the drive, but the frequency reference entered is 0 or below the minimum frequency, the AUTO or HAND

indicator LED on the HOA keypad will light and the OFF indicator will flash.

No.

Name

Setting Range

Default

Z1-07

Speed Reference Select

0 to 3

1

Setting 0: HOA Keypad

Using this setting, the frequency reference can be input by:
• switching between the multi-speed references from d1-01 to d1-04.
• entering the frequency reference on the operator keypad.

Setting 1: Terminals (analog input terminals)

Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in

Table 5.27

for the input

used.

Table 5.27 Analog Input Settings for Frequency Reference Using Voltage Signals

Terminal

Signal Level

Parameter Settings

Notes

Signal Level

Selection

Function Selection

Gain

Bias

A1

0 to 10 Vdc

H3-01 = 0

H3-02 = 0

(Frequency Reference Bias)

H3-03

H3-04

-10 to +10 Vdc

H3-01 = 1

A2

0 to 10 Vdc

H3-09 = 0

H3-10 = 0

(Frequency Reference Bias)

H3-11

H3-12

Set jumper S1 on the terminal

board to “V” for voltage input.

-10 to +10 Vdc

H3-09 = 1

A3

0 to 10 Vdc

H3-05 = 0

H3-06 = 0

(Frequency Reference Bias)

H3-07

H3-08

Set DIP switch S4 on the

terminal board to “AI”.

-10 to +10 Vdc

H3-05 = 1

Drive

A1 Analog Input 1

0 to 10 V

AC Analog input common

2 k

+V 10.5 V, 20 mA power supply

A2 Analog Input 2

A3 Analog Input 3

Drive

A1 Analog Input 1

AC Analog input common

+V 10.5 V, 20 mA power supply

A2 Analog Input 2

A3 Analog Input 3

4 k

-10 to 10 V

OR

Customer
+/- 10 V
Supply

+10 V

-10 V

Common

Figure 5.53 Setting the Frequency Reference as a Voltage Signal at Terminal A1

Current Input
Input terminals, A1, A2, and A3 can accept a current input signal. Refer to

Table 5.28

for an example to set terminal A2 for

current input.

Table 5.28 Analog Input Settings for Frequency Reference Using a Current Signal

Terminal

Signal

Level

Parameter Settings

Notes

Signal Level

Selection

Function

Selection

Gain

Bias

A2

4 to 20 mA

H3-09 = 2

H3-10 = 0

(Frequency Bias)

H3-11

H3-12

Make sure to set jumper S1 on the

terminal board to “I” for current

input.

0 to 20 mA

H3-09 = 3

5.14 Z: Bypass Parameters

208

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual