O4: maintenance monitor settings – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 336

u
o4: Maintenance Monitor Settings
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
o4-03
(050E)
Cooling Fan Operation
Time Setting
FanElapsTimeCn
Sets the value of the fan operation time monitor U4-03 in units
of 10 h.
Default: 0 h
Min.: 0
Max.: 9999
o4-11
(0510)
U2, U3, and UB-09 to
UB-16 Initialization
Fault Data Init
0: No Reset
1: Reset
0: The drive and bypass keep the previously saved record
concerning fault trace and fault history.
1: Resets the data for the U2-oo, U3-oo, and UB-09 to UB-16
monitors. Setting o4-11 to 1 and pressing the ENTER key erases
fault data in the bypass and drive and returns the display to 0.
Default: 0
Range: 0, 1
o4-19
(113A) Power Unit Price
Energy Price/kWh
Sets the price per 1 kWh to calculate the power rate displayed for
total consumed power (U9-07 to U9-10) and total regenerated
power (U9-11 to U9-14).
Default: 000.00
Min.: 000.00
Max.: 650.00
B.11 o: Operator-Related Settings
336
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual