L: protection function, L1: motor protection, L2: momentary power loss ride-thru – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 330: B.9 l: protection function

Advertising
background image

B.9 L: Protection Function

L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,

frequency detection, fault restarts, overtorque detection, and other types of hardware protection.

u

L1: Motor Protection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L1-01

(0480)

Motor Overload

Protection Selection

Mtr OL Charact

0: OL1 Disabled

1: VT Motor

0: Disabled

1: General purpose motor (standard fan cooled)

The drive may not be able to provide protection when using

multiple motors, even if overload is enabled in L1-01. Set L1-01

to 0 and install separate thermal relays to each motor.

Default: 1

Range: 0, 1

182

L1-02

(0481)

Motor Overload

Protection Time

MOL Time Const

Sets the motor thermal overload protection (oL1) time.

Default: 1.0 min

Min.: 1.0

Max.: 5.0

183

L1-04

(0483)

Motor Overheat Fault

Operation Selection

(PTC input)

Mtr OH Fault Sel

0 : Ramp to Stop

1: Coast to Stop

2: Fast-Stop

Sets stopping method when the motor temperature analog input

(H3-02, H3-06, or H3-10 = E) exceeds the oH4 fault level.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time in

C1-09)

Default: 1

Range: 0 to 2

u

L2: Momentary Power Loss Ride-Thru

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L2-01

(0485)

Momentary Power Loss

Operation Selection

PwrL Selection

0: Disabled

1: Enbl with Timer

2: Enbl whl CPU act

0: Disabled.

Drive trips on Uv1 fault when power is lost.

1: Recover within the time set in L2-02.

Uv1 will be detected if power loss is longer than L2-02.

2: Recover as long as CPU has power.

Fdv is not detected.

Default: 2

Range: 0 to 2

183

L2-02

(0486)

Momentary Power Loss

Ride-Thru Time

PwrL Ridethru t

Sets the Power Loss Ride-Thru time. Enabled only when

L2-01 = 1.

Default: 0.5 s

Min.: 0.0

Max.: 2.5

184

L2-03

(0487)

Momentary Power Loss

Minimum Baseblock

Time

PwrL Baseblock t

Sets the minimum wait time for residual motor voltage decay

before the drive output reenergizes after performing Power

Loss Ride-Thru.

Increasing the time set to L2-03 may help if overcurrent or

overvoltage occur during Speed Search or during DC Injection

Braking.

Default:

<1>

Min.: 0.1 s

Max.: 5.0 s

184

L2-21

(04F7)

Low Input Voltage

Detection Level

AVV Detect evel

Set the level at which to detect a low input voltage.

Default: 150 V
Min.: 100 V

<2>

Max.: 230 V

<2>

L2-27

(04F7)

Power Supply

Frequency Fault

Detection Width

FDV Detect Width

Sets the frequency width to use to detect power supply

frequency fault (Fdv).

Default: 6.0 Hz

Min.: 3.0 Hz

Max.: 20.0 Hz

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Values shown are specific to 208 Vac. Double the value for 480 Vac.

B.9 L: Protection Function

330

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual