C: tuning, C1: acceleration and deceleration times, C2: s-curve characteristics – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 316: C4: torque compensation, B.4 c: tuning

Advertising
background image

B.4 C: Tuning

C parameters are used to adjust the acceleration and deceleration times and carrier frequency selections.

u

C1: Acceleration and Deceleration Times

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C1-01

(0200)

Acceleration Time 1

Accel Time 1

Sets the time to accelerate from 0 to maximum frequency.

Default: 30.0 s

Min.: 0.1

Max.: 6000.0

153

C1-02

(0201)

Deceleration Time 1

Decel Time 1

Sets the time to decelerate from maximum frequency to 0.

153

C1-09

(0208)

Fast Stop Time

Fast Stop Time

Sets the time for the Fast Stop function.

Default: 10.0 s

Min.: 0.1

Max.: 6000.0

153

u

C2: S-Curve Characteristics

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C2-01

(020B)

S-Curve Characteristic

at Accel Start

SCrv Acc @ Start

The S-curve can be controlled at the four points shown below.

Run Command

Time

Output Frequency

C2-01

0.20 s

C2-02

0.20 s

ON

OFF

Default: 0.20 s

Min.: 0.00

Max.: 10.00

153

C2-02

(020C)

S-Curve Characteristic

at Accel End

SCrv Acc @ End

Default: 0.20 s

Min.: 0.00

Max.: 10.00

153

u

C4: Torque Compensation

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C4-01

(0215)

Torque Compensation

Gain

Torq Comp Gain

Sets the gain for the automatic torque (voltage) boost function

and helps to produce better starting torque. Used for motor 1.

Default: 1.00

Min.: 0.00

Max.: 2.50

154

C4-02

(0216)

Torque Compensation

Primary Delay Time 1

Torq Comp Time

Sets the torque compensation filter time.

Default:

<1>

Min.: 0 ms

Max.: 60000 ms

<1> Default setting is determined by parameter o2-04, Drive Model Selection.

B.4 C: Tuning

316

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual