Memobus/modbus data table, Command data, D.9 memobus/modbus data table – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 394

Advertising
background image

D.9 MEMOBUS/Modbus Data Table

The tables below list all MEMOBUS/Modbus data.

u

Command Data

It is possible to both read and write command data.

Note:

Bits that are not used should be set to 0. Refrain from writing to reserved registers.

Register No.

Contents

0000H

Reserved

0001H

Operation Commands and Multi-function Inputs

bit 0

H5-12 = 0: Forward Run Command (0 = Stop, 1 = Forward Run)

H5-12 = 1: Run Command (0 = Stop, 1 = Run)

bit 1

H5-12 = 0: Reverse Run Command (0 = Stop, 1 = Reverse Run)

H5-12 = 1: Forward/Reverse (0 = Forward, 1 = Reverse)

bit 2

Option Card External Fault (EF0)

bit 3

Fault Reset

bit 4

Multi-Function Input 1

Function is ComRef when H1-01 = 40 (Forward/Stop).

Note:

When the bit at ComCtrl is turned on, commands from MEMOBUS/Modbus

communications take control of the operation. However, when a communications option

card is connected, that option card is given priority.

bit 5

Multi-Function Input 2

Function is ComCtrl when H1-02 = 41 (Reverse/Stop).

bit 6

Multi-Function Input 3

bit 7

Multi-Function Input 4

bit 8

Multi-Function Input 5

bit 9

Multi-Function Input 6

bit A

Multi-Function Input 7

bit B

Multi-Function Input 8

bit C to F

Reserved

0002H

Frequency Reference Units are determined by parameter o1-03.

0003H

Output voltage gain/

Unit: 0.1%

Range: 20 (2.0%) to 2000 (200.0%), Default when power on: 1000 (100.0%)

0004H

Torque Reference/Torque Limit, 0.1% units, signed (Usable only if Torque Control is enabled)

0005H

Torque Compensation, 0.1% units, signed (Usable only if Torque Control is enabled)

0006H

PID Target, 0.01% units, signed

0007H

Analog Output Terminal FM Setting (10 V / 4000 H)

0008H

Analog Output Terminal AM Setting (10 V / 4000 H)

0009H

Settings for Multi-Function Digital Outputs
bit 0

Multi-Function Contact Output 1 (terminal M1-M2)

bit 1

Multi-Function Contact Output 2 (terminal M3-M4)

bit 2

Multi-Function Contact Output 3 (terminal MD-ME-MF)

bit 3 to 5

Reserved

bit 6

Enables the function in bit 7

bit 7

Fault Contact Output (terminal MA/MB-MC)

bit 8 to F

Reserved

000AH

Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000

000BH to 000EH

Reserved

D.9 MEMOBUS/Modbus Data Table

394

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising