Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 121

Advertising
background image

No.

Name

LCD Display

Description

Values

Page

Z3-03

(8502)

Serial Communications

Baud Rate Select

Baud Rate

0: 1200

1: 2400

2: 4800

3: 9600

4: 19200

5: 38400

6: 57600

7: 76800

8: 115200

Selects the bypass serial communications speed.

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Default: 3

Range: 0 to 8

221

Z3-04

(8503)

Serial Communications

Parity Select

Parity

0: No Parity

1: Even Parity

2: Odd Parity

Selects the bypass serial communications parity.

0: No Parity

1: Even Parity

2: Odd Parity

Default: 0

Range: 0 to 2

221

Z3-05

(8504)

Serial Communications

Fault Select

Fault Sel

0: Ignore

1: Alarm only

2: Fault Send EF0

3: Flt EF0 Open K3

4: Alarm(Z3-10)

Selects the action to take when a serial communications fault

is detected.

0: Ignore. A serial communications loss will result in no action

being taken.

1: Alarm only.

2: Fault with EF0. An EF0 will be sent to the drive. If running

in Bypass mode, the bypass contactor will NOT open and the

motor will keep running.

3: Fault with EF0 and Open Contactors. An EF0 fault will be

sent to the drive and the bypass contactor (K3) will be opened.

4: Alarm and run at preset speed set in Z3-10. Display AL14

alarm on Operator.

Default: 1

Range: 0 to 4

221

Z3-06

(8505)

Serial Communications

Fault Time Select

Fault Time

Sets the time allowed to elapse since receiving serial

communications before triggering a communications fault.

A setting of 0.0 will never time out.

Default: 2.0 s

Min.: 0.0

Max.: 99.9

221

Z3-07

(8506)

Serial Communications

Receive to Transmit

Wait Time

Rx to Tx Wait

Sets the time to delay a serial communications response to a

serial communications command.

Default: 5 ms

Min.: 0

Max.: 99

221

Z3-08

(8507)

BACnet Device Object

Identifier 0

BAC Dev ID0

BACnet only.

Sets the least significant word of 22-bit virtual address.

Default: 1

Min.: 0

Max.: FFFF

222

Z3-09

(8508)

BACnet Device Object

Identifier 1

BAC Dev ID1

BACnet only.

Sets the most significant word of 22-bit virtual address.

Default: 0

Min.: 0

Max.: 003F

222

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Values shown are specific to 208 Vac. Double the value for 480 Vac.
<3> Default setting is dependent on parameter o2-04, Drive Model Selection.
<4> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.

4.3 The Drive and Programming Modes

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

121

4

Start-Up Programming & Operation