background image

4.5 Application Selection

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these

Application Presets automatically assigns functions to the input and output terminals, and sets certain parameters to values

appropriate for the application that was selected.
An Application Preset can either be selected from the Application Selection display in the Setup Group (

Refer to Quick

Setting Parameters on page 120

) or in parameter A1-06. The following presets can be selected:

Note:

An Application Preset can only be selected if all drive parameters are on at their original default settings. It may be necessary to initialize

the drive by setting Z1-01 to 1 or 3 prior to selecting an Application Preset.

WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change the

I/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.

Table 4.6 Application Selection

No.

Name

LCD Display

Description

Values

A1-06

(0127)

Application Preset

Application Sel

0: General

1: Fan General

2: Fan PID

3: Fan ReturnAir/PID

4: Cooling Tower

5: CoolingTower/PID

6: Pump Secondary

7: Pump PID

0: Standard

1: Fan

2: Fan with PID Control

3: Return Fan with PID Control

4: Cooling Tower Fan

5: Cooling Tower Fan with PID Control

6: Pump (Secondary)

7: Pump with PID Control

Default: 0

Range: 0 to 7

u

Setting 1: Fan Application

Table 4.7 Fan: Parameter Settings

No.

Name

Default Setting

b1-03

Stopping Method Selection

1: Coast to Stop

b1-04

Reverse Operation Selection

1: Reverse operation disabled

C1-01

Acceleration Time 1

60 s

L5-01

Number of Auto Restart Attempts

10

L6-01

Torque Detection Selection 1

5: UL3 at speed agree (Alarm)

u

Setting 2: Fan with PID Control Application

Table 4.8 Fan with PID Control: Parameter Settings

No.

Parameter Name

Default Setting

b1-03

Stopping Method Selection

1: Coast to Stop

b1-04

Reverse Operation Selection

1: Reverse operation disabled

b5-01

PID Function Setting

1: Output frequency = PID output 1

b5-03

Integral Time Setting (I)

30 s

b5-08

PID Primary Delay Time Constant

2 s

b5-13

PID Feedback Low Detection Level

2%

b5-14

PID Feedback Low Detection Time

25 s

C1-01

Acceleration Time 1

60 s

L5-01

Number of Auto Restart Attempts

10

L6-01

Stall Prevention Selection during Deceleration

5: UL3 at speed agree (Alarm)

u

Setting 3: Return Fan with PID Control Application

Table 4.9 Return Fan with PID Control: Parameter Settings

No.

Parameter Name

Default Setting

b1-03

Stopping Method Selection

1: Coast to Stop

b1-04

Reverse Operation Selection

1: Reverse operation disabled

b5-01

PID Function Setting

1: Output frequency = PID output 1

b5-03

Integral Time Setting (I)

30 s

4.5 Application Selection

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual