L8: drive protection – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 192

Advertising
background image

Setting 0: Fbase Motor Load Enabled
Setting 1: Fmax Base Motor Load Enabled

UL Detection Level

L6-02

(0 to 300%)

0

Fmin

Fbase

1/f

Fmax

Output
Frequency

L6-14

Motor Underload

Protection at Fmin

Figure 5.49 Motor Underload Protection

n

L6-14: Motor Underload Protection Level at Minimum Frequency

Sets the UL6 detection level at minimum frequency by percentage of drive rated current

No.

Name

Setting Range

Default

L6-14

Motor Underload Protection Level at Minimum Frequency

0 to 300%

15%

u

L8: Drive Protection

n

L8-02: Overheat Alarm Level

Sets the overheat alarm (oH) detection level.
The drive outputs an alarm when the heatsink temperature exceeds the overheat alarm level. If the drive is set to continue

operation after this alarm occurs (L8-03 = 4) and the temperature reaches the overheat fault level, the drive will trigger an oH1

fault and stop operation.
When an output is set for the oH pre-alarm (H2-oo = 20), the switch closes when the heatsink temperature rises above L8-02.

No.

Name

Setting Range

Default

L8-02

Overheat Alarm Level

50 to 150 °C

Det. by o2-04

n

L8-05: Input Phase Loss Protection Selection

Enables or disables the input phase loss detection.

No.

Name

Setting Range

Default

L8-05

Input Phase Loss Protection Selection

0, 1

1

Setting 0: Disabled
Setting 1: Enabled

Enables input phase loss detection. Since measuring the DC bus ripple detects input phase loss, a power supply voltage

imbalance or main circuit capacitor deterioration may also trigger a phase loss fault (PF).
Detection is disabled if:
• The drive is decelerating.
• No Run command is active.
• Output current is less than or equal to 30% of the drive rated current.

5.8 L: Protection Functions

192

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual