HOA Keypad Display

Fault Name

Parameters related to Speed Search are set

incorrectly

• Check values set to Speed Search related parameters.
• Reduce the Speed Search Operation Current Level 1 (Current Detection Type 2) (b3-31).
• After Auto-Tuning, set b3-24 to 1 to enable Speed Estimation Speed Search.

Output current fluctuation due to power supply

loss

Check the power supply for phase loss.

HOA Keypad Display

Fault Name

oL2

Overload
The thermal sensor of the drive triggered overload protection.

Cause

Possible Solution

Load is too heavy

Reduce the load.

Acceleration or deceleration time is too short

Increase the settings for the acceleration and deceleration times (C1-01 and C1-02).

The output voltage is too high

• Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not lower E1-08 and E1-10 excessively. This reduces load tolerance at low speeds.

Drive capacity is too small

Use a larger drive.

Overload occurred when operating at low speeds

• Reduce the load when operating at low speeds.
• Use a larger drive.
• Lower the carrier frequency (C6-02).

Excessive torque compensation

Reduce the torque compensation gain in parameter C4-01 until there is no speed loss but less current.

Parameters related to Speed Search are set

incorrectly

• Check the settings for all Speed Search related parameters.
• Adjust the current used during the Speed Search deceleration time (b3-03).
• After Auto-Tuning, set b3-24 to 1 to enable Speed Estimation Speed Search.

Output current fluctuation due to input phase loss Check the power supply for phase loss.

HOA Keypad Display

Fault Name

oL3

Overtorque Detection 1
The current has exceeded the value set for Torque Detection Level 1 (L6-02) for longer than the

allowable time (L6-03).

Cause

Possible Solution

Parameter settings are not appropriate for the load Check L6-02 and L6-03 settings.
Fault on the machine side (e.g., machine is locked

up)

Check the status of the load. Remove the cause of the fault.

HOA Keypad Display

Fault Name

oL4

Overtorque Detection 2
The current has exceeded the value set for Torque Detection Level 2 (L6-05) for longer than the

allowable time (L6-06).

Cause

Possible Solution

Parameter settings are not appropriate for the load Check the settings of parameters L6-05 and L6-06.

HOA Keypad Display

Fault Name

oL5

Mechanical Weakening Detection 1
Overtorque occurred, matching the conditions specified in L6-08.

Cause

Possible Solution

Overtorque triggered mechanical weakening

detection level set to L6-08

Identify the cause of mechanical weakening.

HOA Keypad Display

Fault Name

oPr

HOA Keypad Connection Fault
The HOA keypad has been disconnected from the drive.

An oPr fault will occur when all of the following conditions are true:
• Output is interrupted when the keypad is disconnected (o2-06 = 1).
• The Run command is assigned to the keypad (b1-02 = 0 and OFF mode has been selected).

Cause

Possible Solution

6.4 Fault Detection

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

247

6

Diagnostics & Troubleshooting