Pid output fault – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 272

Advertising
background image

n

Oscillation or Hunting

Cause

Possible Solutions

Gain is too low when using PI control.

Refer to b5: PID Control on page 142

for details.

The frequency reference is assigned to an external

source and the signal is noisy.

• Ensure that noise is not affecting the signal lines.
• Separate main circuit wiring and control circuit wiring.
• Use twisted-pair cables or shielded wiring for the control circuit.
• Increase the analog input time filter constant (H3-13).

The cable between the drive and motor is too long.

• Perform Auto-Tuning for line-to-line resistance.
• Reduce the length of the cable.

u

PID Output Fault

Cause

Possible Solutions

No PID feedback input.

• Check the multi-function analog input terminal settings.
• Set multi-function analog input terminal A1, A2, or A3 for PID feedback (H3-02, H3-10, or

H3-06 = B).

• A signal input to the terminal selection for PID feedback is needed.
• Check the connection of the feedback signal.
• Check the various PID-related parameter settings.
• No PID feedback input to the terminal causes the value detected to be 0, causing a PID fault

and the drive to operate at max frequency.

The level of detection and the target value do not

correspond with each other.

• PID control keeps the difference between target and detection values at 0. Set the input level

for the values relative to one another.

• Use analog input gains H3-03, H3-07, and H3-11 to adjust PID target and feedback signal

scaling.

Reverse drive output frequency and speed detection.

When output frequency rises, the sensor detects a

speed decrease.

Set PID output for reverse characteristics (b5-09 = 1).

Adjustment made to PID parameter settings are

insufficient.

Refer to b5: PID Control on page 142

for details.

u

Motor Rotates after the Drive Output is Shut Off (Motor Rotates During DC Injection
Braking)

Cause

Possible Solutions

DC Injection Braking is set too low and the drive

cannot decelerate properly.

• Adjust the DC Injection braking settings.
• Increase the current level for DC Injection Braking Current (b2-02).
• Increase the DC Injection Braking time at stop (b2-04).

The stopping method is set so that the drive coasts to

stop.

Set b1-03 (Stopping Method Selection) to 0 or 2.

u

Output Frequency is Not as High as Frequency Reference

Cause

Possible Solutions

Frequency reference is set within the range of the Jump

frequency.

• Adjust the parameters used for the Jump frequency function (d3-01, d3-02, d3-03).
• Enabling the Jump frequency prevents the drive from outputting the frequencies specified in

the Jump range.

Upper limit for the frequency reference has been

exceeded.

• Set the maximum output frequency and the upper limit for the frequency reference to more

appropriate values (E1-04, d2-01).

• The following calculation yields the upper value for the output frequency:

E1-04 x d2-01 / 100

Large load triggered Stall Prevention function during

acceleration.

• Reduce the load.
• Adjust the Stall Prevention level during acceleration (L3-02).

6.9 Troubleshooting without Fault Display

272

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising