u

E2: Motor 1 Parameters

These parameters contain the motor data needed for motor 1. Enter the motor data into these parameters when Auto-Tuning

cannot be performed.

n

E2-01: Motor Rated Current

Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on

the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.

No.

Parameter Name

Setting Range

Default

E2-01

Motor Rated Current

10% to 150% of the drive

rated current

<1>

Determined by

o2-04

<1> Display is in the following units based on drive model:

2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units

Note:

An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly to

prevent this error.

n

E2-03: Motor No-Load Current

Set the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive sets

E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 2, 3). The motor no-load current

listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to receive a copy of the

motor test report.

No.

Parameter Name

Setting Range

Default

E2-03

Motor No-Load Current

0.00 A to [E2-01]

<1>

Determined by

o2-04

<1> Display is in the following units based on drive model:

2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units

5.5 E: Motor Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual